SOLENOID PART NO. 890181
SINGLE SOLENOID
TB6
R1+
S
R1-
2
3
R2+
1
R2-
NOTE: MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 0.6 OHMS.
SOLENOID PART NO. 48650001
SINGLE SOLENOID
TB6
RED
R1+
R1-
S
R2+
BLK
R2-
NOTE:
MAXIMUM CIRCUIT WIRING RESISTANCE
Details of Wiring Kidde Control Head Solenoids to Release Circuit Terminals
FM GROUP A SOLENOIDS
S
NOTE: MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 2.3 OHMS.
Details of Wiring FM Sprinkler Solenoids to Release Circuit Terminals
November 2002
TWO SOLENOIDS
2
S
3
TB6
R1+
1
R1-
2
S
3
R2+
1
R2-
TWO SOLENOIDS
TB6
S
RED
R1+
CKT #1
BLK
R1-
RED
R2+
CKT #2
BLK
R2-
S
IS TO BE 6.0 OHMS.
SINGLE SOLENOID
TB6
R1+
R1-
R2+
R2-
FM GROUP E & G SOLENOIDS
S
NOTE:
MAXIMUM CIRCUIT WIRING RESISTANCE
Figure E-7. Release Circuit and Stop Valve Terminal Detail
firealarmresources.com
SOLENOID PART NO. 899175
SINGLE SOLENOID
MICROSWITCH
S
BLK
BLU
YEL
WHT
SOLENOID
SAFETY FUSE
NOTE: MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 0.6 OHMS.
SOLENOID PART NO. 81-100000-001
SINGLE SOLENOID
TB6
RED
R1+
R1-
S
R2+
BLK
R2-
NOTE:
MAXIMUM CIRCUIT WIRING RESISTANCE
FM GROUP B & D SOLENOIDS
S
NOTE:
MAXIMUM CIRCUIT WIRING RESISTANCE
TB6
R1+
R1-
R2+
R2-
IS TO BE 2.5 OHMS.
E-5
Kidde Gemini II System
TWO SOLENOIDS
S
TB6
TB6
BLK
R1+
BLU
YEL
WHT
R1-
BLK
BLU
R2+
YEL
WHT
R2-
S
TWO SOLENOIDS
S
TB6
RED
CKT #1
BLK
RED
CKT #2
BLK
S
IS TO BE 3.7OHMS.
SINGLE SOLENOID
TB6
R1+
R1-
R2+
R2-
IS TO BE 1.5 OHMS.
06-235975-001
R1+
R1-
R2+
R2-
R1+
R1-
R2+
R2-