Walk Test™ PROCEDURES,
How to Enable a
3.
Disabled Point,
(continued)
WARNING
If the enable process is successful, the following message is shown on the alphanumeric
display.
4.
5.
What to do in Case
CALL YOUR LOCAL SIMPLEX BRANCH OFFICE, WHICH IS LISTED IN THE
of System
YELLOW PAGES, FOR ALL MALFUNCTIONS, OR IF YOU WOULD LIKE A
Malfunction
QUALIFIED SIMPLEX TECHNICIAN TO ASSIST YOU WITH INSTALLATION,
TESTING AND TROUBLESHOOTING THE SYSTEM.
Continued
Press the <ENTER> key. The alphanumeric display shows the following message.
Please stand by . . .
ZONE 12 will ENABLE in 60 seconds
If the zone is still in alarm, a WARNING is displayed which tells you
that the system will sound an alarm if the timer (60 seconds) times out.
TO ABORT THE ENABLE, PRESS THE <DISABLE> KEY. If an
alarm condition exists, the following is shown on the alphanumeric
display.
** WARNING ** Press <DISABLE> to abort
ZN12 will ALARM in 60 seconds
IF THE ABOVE WARNING IS SHOWN ON the ALPHANUMERIC
DISPLAY, PRESS the <DISABLE> OR AN <ACK> KEY. FAILURE
TO ABORT THE ENABLE WILL CAUSE AN ALARM
CONDITION.
ENABLE COMPLETED
Repeat steps 1 through 3 above to enable required points.
Press the <CLR> key to exit. This will allow the panel to show the Time and Date.