7.3.5 Water fill time
Used to set the time period for which the water inlet valve remains open. The time is expressed in seconds.
Range from 1 to 250.
7.3.6 Water drain time
Usedtosetthetimeperiodforwhichthedrainremainsopentoallowasmallamountofwatertodrainoutofthetank.Thetime
is expressed in seconds. Range from 1 to 250.
7.3.7 AT coefficient
RESERVED - DO NOT CHANGE
7.3.8 Water change interval
Indicatestheintervalbetweenfullwaterchangesinthetank.Thetimeisexpressedinhours.
7.3.9 Manual water drainage
Reset
for 5 seconds; the text MAINTENANCE will appear on the display.
Todrainthewatermanually,pressandhold
NOTE: Switch the humidifier off and on again every time manual drainage is carried out.
7.3.10 Nominal current setting
RESERVED - DO NOT CHANGE
7.3.11 Wash time
Sequenceofafillingcycleandadraincycle,andthesubsequentreintroductionofsteamproductioninordertodilutethe
concentrationofmineralsaltsinsidetheboilertank.
7.3.12 0-10 V signal calibration coefficient
RESERVED - DO NOT CHANGE
7.3.13 DP Enabling
RESERVED - DO NOT CHANGE
7.3.14 ModBus Address
ModBus addressing
7.3.15 ModBus Speed
ModBus speed parameter setting
7.3.16 Empty Tank Test
RESERVED - DO NOT CHANGE
7.3.17 Drain due to inactivity time
Intheabsenceofarequestforhumidity,withthehumidifieractivebutinstandby,thedrainduetoinactivityprocedureis
enabledonce24hourshavepassedwithouthumiditybeingrequested.Theparametercanbesettoavaluebetween1and48
hours depending on the characteristics of the supply water and on the sanitary requirements of the installation.
7.3.18 RTH ramp
Procedure for managing the internal proportional system in accordance with the incoming signal.
RESERVED - DO NOT CHANGE
924VHE4.02 - VEH series humidifiers