2. TECHNICAL DATA

2.1 Technical specifications

Description
Steam production
Production capacity
Pressure limits
Electrical properties
Power absorbed
Power supply
Phases
Absorption per phase
Hydraulic properties
Supply water quality
Supply water conductivity
Supply water hardness
Minimum supply flow rate
Supply water pressure
Supply water connection
Water drain outer diameter
General specifications
Dimensions
Weight (hydraulic module)
Electric panel IP protection degree
Hydraulic module IP protection
degree
Maximum installation altitude
Regulation
Control type
Control signal
Compliance
CE
NOTE: The • symbol indicates that the data applies to every p/n; for further information please contact the ELSTEAM sales
office.
(*): Steam production occurs inside the AHU and therefore under equivalent pressure conditions.
924VHE4.02 - VEH series humidifiers
MU
VEH10XS VEH20•• VEH30• VEH40• VEH60•• VEH80L VEH100XL
kg/h
10
20
Pa/bar There are no pressure limits (*)
kW
7.5
15
V,Hz
400Vac,50/60
Ph
3
A
11
22
---
See section "5.2.1 WATER SPECIFICATIONS" ON PAGE 17
μS*cm 70...1250
°f
5...50
l/h
300
MPa/bar 0.02...1/0.2...10
---
M 3/4" GAS
mm (in.) 40 (1.57)
mm (in.) See section "4.1 DIMENSIONS" ON PAGE 12
kg
15
18
---
IP54
---
IPX0
m (ft.)
≤2000(6561.6)
---
Integrated or remote
Integrated: 4...20 mA
---
Remote:
Proportional(0...10V),ON-OFFor(0...10V/4...20mA)
---
Yes,withself-certification
| 10 |
30
40
60
22.5
30
45
32
43
65
20
24
26
80
100
60
75
87
108
31
33
02/2022