Keys; Menu; Switching On/Off; Language - Elsteam VEH Series Manual

Immersed electrode humidifiers for air handling units
Hide thumbs Also See for VEH Series:
Table of Contents

Advertisement

7.2 Keys

-
Reset
•  G obackinthe
Press and

menu

hold 5 s for
• Decrease the
Maintenance and
value
Drain procedure
7.3 Menu
The VEH series humidifier menu includes the following entries:
• ON/OFFmode(U);
• Language (U);
• Humidity control (U);
• Emptying time (RESERVED - DO NOT CHANGE);
• Waterfilltime(M);
• Water drain time (M);
• ATcoefficient(RESERVED - DO NOT CHANGE);
• Minimum input setting 0...10 V (M);
• Water change interval (M).
NOTE: (U) Parameters that can be changed by the user;
(M) Parameters that can only be changed by the installer or maintenance technician.
MALFUNCTIONING OF THE EQUIPMENT
• ParametersmarkedasRESERVEDmustonlybechangedbyELSTEAMpersonnel.
• AnychangesnotmadebyELSTEAMpersonneltoparametersmarkedasRESERVEDareunauthorisedandwillimmediately
invalidate the product warranty.
• ELSTEAMdoesnotassumeresponsibilityforchangesmadetoparametersmarkedasRESERVEDbypersonnelnot
expressly authorised by ELSTEAM itself.
7.3.1 Switching on/off 
To switch the VEHdehumidifieronoroff,presstheswitchonthefrontoftheelectricpanel.
Whenthemachineisswitchedon,itemptiesthetankbyactivatingtheelectricdrainvalveforanemptyingtimeT.Ifsteam
productionisrequired,onceemptyingiscomplete,thewaterfillingprocedurebeginsinthrottledmodesoastoallowahigh
levelofheatingefficiency,untiltherequiredpowerisreached.
NOTE: The isolator installed externally must be made operational before the humidifier is switched on.

7.3.2 Language

You can set the desired language by selecting one of the 4 available options:
• Italian.
• English.
• French.
• German
Default: Italian

7.3.3 Humidity control

Humidity control can be selected from the following options:
•  I nternal:inthiscaseyouwillbeaskedtosetthehumidityasdesiredbetween0and100%,usinga4...20mAprobewhich
should be connected as described in the section "6.3 WIRING DIAGRAM" ON PAGE 24.
• External: in this case the choice concerns the type of humidistat used:
• ON/OFFtype;
• Proportional type in voltage 0...10 V;
• Proportional type in current 4...20 mA.

7.3.4 Emptying time

RESERVED - DO NOT CHANGE
924VHE4.02 - VEH series humidifiers
Keys
+
• Go forward in the
Confirmthe
menu
value on the
• Increase the
display
value
NOTICE
OK
SET
Enter the system
configuration
menu
| 26 |
Combinations
+
Reset
Reset
+
Increase display
Decrease display
backlighting
backlighting
brightness
brightness
-
+
02/2022

Advertisement

Table of Contents
loading

Table of Contents