5. INSTALLATION

5.1 Humidifier parts

5.1.1 Top

• Steam outlet;
• Male3/4"GASconnectorforwatersupply.

5.1.2 Bottom

• Water outlet to connect to sewer system;
• Strain relief cable gland for power supply wiring;
• Strain relief cable gland for wiring of regulation board.

5.2 Water connections

You will need the following components to plumb in the humidifier:
• An intercept tap;
• Asupplementaryfiltertotheonealreadyinthesolenoidvalve;
• A pressure reducer (if the pressure of the mains water exceeds 1 MPa (10 bar)).
N.B.:Ifapressurereducerisused,makesureitiseffectiveanddoesnotcauseadrasticreductioninpressurewhenthemains
pressure is very low.
MALFUNCTIONING OF THE EQUIPMENT
• The feed water must have a minimum pressure of 0.2 MPa (2 bar).
• Connect the solenoid valve to the mains using the flexible hose supplied to reduce water hammers in the hose to the
humidifier.
• Duringinstallation,becarefulnottodamagetheplasticthreadofthesolenoidvalve.
• Whenmakingthewaterconnections,itmustalwaysbepossibletoaccessthemechanicalfilterinthewaterloadsolenoid
valve for cleaning.

5.2.1 Characteristics of water

• Water pressure between 0.2...1 MPa (2...10 bar);
• Temperaturebetween1...50°C(33.8...122°F);
• Conductivitybetween75...1250μS/cm;
• Maximum water hardness between 5...50 °f.
N.B.:Ifwaterisharderorifthereismoreorganicresidueinit,thehumidifierwillstilloperatecorrectlybutitmustbeserviced
more regularly.
Dos
• Flushwaterintothedrainforacoupleofhoursbeforemakingthefinalconnection.
•  C hecktheconditionoftherubbercouplingregularlytopreventproblemsandwaterleakingintotheroom.
Don'ts
•  S oftenthewater.Ifthewaterhardnessisabove50°forifitissuchthattheboilerrequiresregularmaintenance,use
demineralisedwatermixedwithtapwaterinapercentagethatensuresaminimumconductivityof200μS/cmanda
hardness of at least 10 °f.
MALFUNCTIONING OF THE EQUIPMENT
• Do not use softened water.
• Oncethehumidifierhasbeeninstalled,flushthepipeswiththeremainingwatertopreventblockingthefilter.
• Checkallthepartsofthehumidifierareintact.
• Ifevenonepartofthehumidifierisdamaged,suspendinstallation.

5.3 Water discharge system

Asthishumidifierhasanautomaticboilercleaningfunction,thewateroutletmusthaveacapacityofatleast10litresinafew
seconds (maximum 1 l/s).
MALFUNCTIONING OF THE EQUIPMENT
Sizetheoutletpipetopreventobstructionsorblockagesduringtheautomaticcleaningcycle.
924KTE4.01 - KT series humidifiers