AHU Electrodes Humidifier - VEH
10.5 Drain time.
Set the time during which the drain system remains open to allow emptying of the tank. The time
is in seconds, from 1 to 250.
Default 120".
10.6 Water fill time
Set the time during which the inlet valve is open water. The time is in seconds, from 1 to 250.
Default 10".
10.7 Purge Time.
Set the purge time during which the drain system remains open to allow a small discharge of
water. The time is in seconds, from 1 to 250.
Default 1".
10.8 Heating time
Set the waiting time during which the water in the tank is heated by the passage of the current.
The time is in seconds, from 1 to 1200 (= 20min.).
Default 80".
10.9 TA coefficient.
Set the coefficient for the TA mounted in the humidifier. It is a number from 10 to 9999, modified
in steps of 10.
Default 750.
10.10 Level sensor
Set the type of level sensor connected. Can be chosen among:
•
HV Level switch (High Voltage). Input IN-DIG0
•
Contact with float on input IN-DIG1 (jumper JP2 must be closed):
a. N.C. = normally closed.
b. N.O. = normally open.
Default HV Level switch
10.11 Pressure threshold
2000Pa
10.12 Minimum 0-10V Input Calibration
This parameter allows varying the minimum threshold for intervention in the case of using an
external controller with different voltages from 0-10V.
10.13 Water change interval
It indicates the interval between complete changes of water in the kettle.
(Default 4h)