EHPN Series High-pressure air humidifiers WARNING Make sure you read and fully understand the manual before using this device. Non-observance of these instructions may result in death Operating and maintenance manual or serious injury. 924EHPNE4.01 - 02/2024...
IMPORTANT INFORMATION Liability and residual risks ELSTEAM assumes no liability for any damage caused by the following (by way of example; this is not an exhaustive list): • I nstallation/useforpurposesotherthanthosespecifiedand,inparticular,notadheringtothesafetyprovisionsset out by current regulations in the country in which the product is installed and/or contained in this manual;...
Only suitably trained and experienced personnel capable of understanding the content of this manual and all documentation regardingtheproductareauthorisedtoworkonandwiththisequipment.Furthermore,thepersonnelmusthavecompleted coursesinsafetyandmustbeabletorecogniseandpreventtheimplieddangers.Thepersonnelmusthavesuitabletraining, knowledgeandexperienceatatechnicallevel,andbecapableofanticipatinganddetectingpotentialriskscausedbyusing theproduct,aswellaschangingthesettingsandmodifyingthemechanical,electricandelectronicequipmentfortheentire systeminwhichtheproductisused.Allpersonnelworkingonandwiththeproductmustbeentirelyfamiliarwiththerelevant standardsanddirectives,aswellassafetyregulations. UNAUTHORIZED PERSONNEL The humidifier must notbeusedbypersons(includingchildren)withreducedphysical,sensoryormentalcapabilitiesor personswithnoexperienceorknowledge. 924EHPNE4.01 - EHPN series humidifiers | 7 | Important safety information | 02/2024...
SAFETY INFORMATION RELATING TO THE PRODUCT EHPN series humidifiers are defined as "NOT ACCESSIBLE TO THE PUBLIC". Beforecarryingoutanyworkontheequipment,readtheseinstructionscarefully,makingsureyouunderstandeverything. DANGER RISK OF ELECTRIC SHOCK, EXPLOSION OR ELECTRIC ARC • Only use electrically insulated measuring devices and equipment. • Do not install the equipment while the power supply is connected.
• Intheeventofpoormaintenance/cleaningafterthehumidifierhasbeenshut-downforalongtime,microorganisms (including the bacteria that cause Legionellosis) may proliferate and be transferred into the air treatment system. • Thehumidifiermustbeusedproperlyandbemaintainedandcleanedproperlyatprescribedintervals,asdescribedinthe MAINTENANCE chapter. 924EHPNE4.01 - EHPN series humidifiers | 9 | Safety information related to health and hygiene | 02/2024...
The EHPN series adiabatic humidification system regulates its operation according to the humidity request from the control systems (see "6.6 CONFIGURATIONS" ON PAGE 49). The droplet separator (optional only installed in the AHU) is used to stop and water droplets that were not atomised before entering the duct.
• Stainless steel pumping system; • EVCO control with EPcolor interface on the pump unit and EVCO control with EV3interfaceonthedistributionrack; • Pump control with real-time display of operating parameters. 924EHPNE4.01 - EHPN series humidifiers | 12 | Introduction | 02/2024...
• Automatic malfunction analysis; • Clear,advanceddiagnostics; • Can be connected to supervision systems via Modbus. 1.4 Applications The EHPN series can be used in various applications including: • Air treatment plants; • Hospital environments where sterile steam is not required; • Industries;...
L=15m EHPNK13 Stainlesssteelunit/rackwaterinletpipe,L=2m Illustrations of some accessories are shown below. 1.6.1 Droplet separator The customer is responsible for installing a droplet separator. An optional ELSTEAM droplet separator is available for the EHPN humidifier. Fig. 3. Droplet separator NOTE: The droplet eliminator of the humidifying system EHPNwasnotintendedtobecleaned.Afterexceedingitslifetime,the droplet separator must have been replaced.
The image is provided for illustrative purposes only and may differ from the product itself. Fig. 4. Reverse osmosis system (example) Inordertoensurecorrectsizingtomeetyourrequirements,youcancontactELSTEAM,whichwillworktogetherwitha partner to propose an appropriate water treatment system. 1.6.3 Antiscalant dosing kit Fig. 5. Antiscalant dosing kit 924EHPNE4.01 - EHPN series humidifiers | 15 | Introduction | 02/2024...
1.6.4 UV lamp Fig. 6. UV lamp 1.6.5 Telescopic support for EHPN rack distribution branches Fig. 7. Telescopic support for EHPN rack distribution branches 924EHPNE4.01 - EHPN series humidifiers | 16 | Introduction | 02/2024...
2. TECHNICAL DATA Chapter content This chapter contains the following information: Subject Page 2.1 Technical specifications ..................18 924EHPNE4.01 - EHPN series humidifiers | 17 | Technical data | 02/2024...
3. RECEIVING THE PRODUCT Chapter content This chapter contains the following information: Subject Page 3.1 Before you start ....................20 3.2 Checking the packaging ..................20 924EHPNE4.01 - EHPN series humidifiers | 19 | Receiving the product | 02/2024...
• Pump user manual; • Yellow oil cap on the pump (vented) to be used for operation; replace with the red one for transport only. • Hexagonalkeytoopenthepumpunit. 924EHPNE4.01 - EHPN series humidifiers | 20 | Receiving the product | 02/2024...
4. DIMENSIONS AND MECHANICAL ASSEMBLY Chapter content This chapter contains the following information: Subject Page 4.1 Dimensions ......................22 4.2 Installing the pump unit ..................24 4.3 Installing the distribution rack ................26 924EHPNE4.01 - EHPN series humidifiers | 21 | Dimensions and Mechanical assembly | 02/2024...
RISK OF ELECTRIC SHOCK, EXPLOSION OR ELECTRIC ARC • Protect the humidifier properly from water and dust. • Installthehumidifierinacoveredbox,observingtheminimuminstallationdistances. • Makesurethehumidifierisprotectedproperlyfromwateranddust. Installation example Fig. 10. Installing the pump unit 924EHPNE4.01 - EHPN series humidifiers | 24 | Dimensions and Mechanical assembly | 02/2024...
0016020016 Telescopic support for EHPNrackdistributionbranches to prevent unexpected operation and/or mechanical faults and to give the branches a slope of 0.2...1° so that they drain fully. 924EHPNE4.01 - EHPN series humidifiers | 26 | Dimensions and Mechanical assembly | 02/2024...
5.2 Plumbing composition of the distribution rack..........32 5.3 Installing the plumbing ..................33 5.4 Water drainage system ..................34 5.5 Distribution in the AHU ..................35 5.6 Distribution in the room ..................36 924EHPNE4.01 - EHPN series humidifiers | 30 | Installing the plumbing | 02/2024...
5.2 Plumbing composition of the distribution rack Fig. 17. Plumbing overview Reference Description Reference Description LED user interface 3/8" G water inlet from the pump unit Distribution branches 1/8" G water drain outlet 924EHPNE4.01 - EHPN series humidifiers | 32 | Installing the plumbing | 02/2024...
2x production capacity (l/min) Optimal properties Description Features Water pressure 0.1...0.3 MPa Water temperature 5...20°C(41..68°F) Electrical conductivity 0...25μS/cm(atatemperatureof20°C(68°F)) Total hardness 0...2 °f Minimum supply flow rate 2x production capacity (l/min) 924EHPNE4.01 - EHPN series humidifiers | 33 | Installing the plumbing | 02/2024...
• Install all equipment in compliance with the technical specifications indicated in the relevant documentation. Cooling coil Droplet separator Fig. 20. AHU installation position NOTE:inambienttemperatureconditionswhichmayleadtotheformationofice,itiswisetotakeallnecessaryprecautionsto prevent the supply water and the drain water from freezing and causing the humidifier to malfunction. 924EHPNE4.01 - EHPN series humidifiers | 35 | Installing the plumbing | 02/2024...
Throttling solenoid valve (NC) Antiscalant Outlet solenoid valve (NO) Pump unit Distribution system Always position the outlet solenoid valve (NO) after the throttlingsolenoidvalve(NC),atthelowestpointinthedistributionline inordertopreventwaterstagnation.Whenthesystemstopsrunning,theoutletsolenoidvalve(NO)mustalwaysensurethat the distribution line is drained fully. 924EHPNE4.01 - EHPN series humidifiers | 36 | Installing the plumbing | 02/2024...
6.3 Electrical composition of the distribution rack ..........41 6.4 Connection best practice ..................42 6.5 Electrical connections ..................46 6.6 Configurations .....................49 6.7 Power supply and earth wiring connection ............52 924EHPNE4.01 - EHPN series humidifiers | 38 | Electrical connections | 02/2024...
Reference Description EVCO Compact series inverter Cable gland for power wiring Pump unit control board Fuseholderbase 230/24 Vac transformer 3 cable glands for signal wiring Earth terminal Userinterface,3.5"TFTgraphicdisplay 924EHPNE4.01 - EHPN series humidifiers | 40 | Electrical connections | 02/2024...
2 x 0.08…0.5 2 x 0.25…0.34 2 x 20...20 25…15 25…15 22...15 22...20 2 x 28…20 2 x 28…20 2 x 23…21 Fig. 27. Suitable wiring for I/O SELV 924EHPNE4.01 - EHPN series humidifiers | 42 | Electrical connections | 02/2024...
Power cable entry on cable gland (PGx depending on model) Signal wiring entry on cable gland PG9 Cable routing in the water section (for motor and stainless steel pump) 924EHPNE4.01 - EHPN series humidifiers | 43 | Electrical connections | 02/2024...
ON OFF LA1 + 2 70...73 ConnectiontomainrackcontrolboardSCI1 ON ON LA1 + 3 Activate termination resistor on SCI1 RS-485 serial line. 74...77 No connection N.C. 1 =SCI1RS-485serialtermination;2=Reserved 78-79 No connection N.C. 924EHPNE4.01 - EHPN series humidifiers | 48 | Electrical connections | 02/2024...
7. PUMP UNIT USER INTERFACE Chapter content This chapter contains the following information: Subject Page 7.1 Interface .......................54 7.2 Menu ........................55 924EHPNE4.01 - EHPN series humidifiers | 53 | Pump unit user interface | 02/2024...
No warranty confirm to proceed S/cm S/cm DONE Fig. 47. First start-up - Setting the electrical conductivity Fig. 48. Setting the electrical conductivity > 100 μS 924EHPNE4.01 - EHPN series humidifiers | 54 | Pump unit user interface | 02/2024...
75 %RH 82.0 bar 62.0 °C 720 rpm 120 l/h Fig. 50. Home screen with humidity sensor alone Top line: Humidity measured by the room humidity sensor. 924EHPNE4.01 - EHPN series humidifiers | 55 | Pump unit user interface | 02/2024...
RESERVED. NOT ACCESSIBLE TO THE PUBLIC. MANUFACTURER Access to change the date/time Currently accessing alarm control ALARMS Access the alarm log HISTORY Reset parameters to factory settings SETTING 924EHPNE4.01 - EHPN series humidifiers | 56 | Pump unit user interface | 02/2024...
Only with CFGp=HUM To change the humidity setpoint: access the user menu as described in the sub-paragraph "8.2.1 USER MENU" ON PAGE 68,and change the value of SP1. 924EHPNE4.01 - EHPN series humidifiers | 57 | Pump unit user interface | 02/2024...
Displays the status of the CV digital input (fan enable) if it is connected. DICV OFF=CV input closed; On=CV input open. Displays the status of the 0/1digitalinput(remoteON/OFF)ifitisconnected. DIOF OFF=0/1 input closed; ON=0/1 input open. 924EHPNE4.01 - EHPN series humidifiers | 58 | Pump unit user interface | 02/2024...
Page 59
Displays the status of the disinfection solenoid valve output. DOEVd OFF=DisinfectionsolenoidvalveoutputOFF; ON=DisinfectionsolenoidvalveoutputON. Displays the status of the dehumidification enable output. DOdeh OFF=DehumidificationenableoutputOFF; ON=DehumidificationenableoutputON. Displays the status of the general alarm output. OFF=GeneralalarmoutputOFF; ON=GeneralalarmoutputON. 924EHPNE4.01 - EHPN series humidifiers | 59 | Pump unit user interface | 02/2024...
Filters The hours of filter operation. The hours of inlet solenoid valve operation. The hours of pump oil operation. Resetting the operating hours Toresettheoperatinghours,tapthe RESET keybesidethecorrespondingvalue. 924EHPNE4.01 - EHPN series humidifiers | 60 | Pump unit user interface | 02/2024...
8. DISTRIBUTION RACK USER INTERFACE Chapter content This chapter contains the following information: Subject Page 8.1 Interface .......................64 8.2 Menu ........................67 924EHPNE4.01 - EHPN series humidifiers |63|Distributionrackuserinterface| 02/2024...
Go to the maintenance and reset operating hours menu • Navigate within the menu • Scroll up through the values Activate manual draining • Navigate within the menu • Confirmthevaluesonthedisplay Enter the main menu • Set/change the humidity setpoint 924EHPNE4.01 - EHPN series humidifiers |64|Distributionrackuserinterface| 02/2024...
HOME screen with proportional regulation (CFG = PROP) Fig. 57. Home screen with proportional regulation (CFG = PROP) Top line: Actualhumidityrequestin%. NOTE: The CV and 0/1 contacts must be closed to produce humidity. 924EHPNE4.01 - EHPN series humidifiers |65|Distributionrackuserinterface| 02/2024...
NOTE: The CV and 0/1 contacts must be closed to produce humidity. 8.1.5 Changing the main sensor humidity setpoint With CFG=HUMorCFG=HUMLonly. To change the humidity setpoint: Touch and release Fig. 60. Changing the humidity setpoint 924EHPNE4.01 - EHPN series humidifiers |66|Distributionrackuserinterface| 02/2024...
Fig. 61. Distribution rack interface menu Menu Description Access the user menu Access the maintenance technician menu RESERVED. NOT ACCESSIBLE TO THE PUBLIC. Currently accessing alarm control Access the alarm log Reset parameters to factory settings 924EHPNE4.01 - EHPN series humidifiers |67|Distributionrackuserinterface| 02/2024...
Sets the humidity limit setpoint`. Humidity limit setpoint See "11.2 REGULATION PARAMETER TABLE FOR THE DISTRIBUTION RACK" ON PAGE 89 Other See "11.2 REGULATION PARAMETER TABLE FOR THE DISTRIBUTION RACK" ON PAGE 89 parameters 924EHPNE4.01 - EHPN series humidifiers |68|Distributionrackuserinterface| 02/2024...
ON=InletsolenoidvalveoutputON. Displays the status of the outlet solenoid valve output. Branch 3 solenoid oEUo OFF=OutletsolenoidvalveoutputOFF; valve output status ON=OutletsolenoidvalveoutputON. Displays the status of the general alarm output. General alarm output OFF=GeneralalarmoutputOFF; status ON=GeneralalarmoutputON. 924EHPNE4.01 - EHPN series humidifiers |69|Distributionrackuserinterface| 02/2024...
Displays the number of branch 2 solenoid valve activations. activations EU3H Branch 3 SV. hours Displays the hours of branch 3 solenoid valve operation. No. branch 3 SV. EU3A Displays the number of branch 3 solenoid valve activations. activations 924EHPNE4.01 - EHPN series humidifiers |70|Distributionrackuserinterface| 02/2024...
The table below contains the labels shown on the display and their descriptions: Top line Bottom line Description Forcesthebranch1solenoidvalveoutputon/off. Branch 1 SV output SEU1 OFF=Branch1solenoidvalveoutputforcedOFF; status ON=Branch1solenoidvalveoutputforcedON. Forcesthebranch2solenoidvalveoutputon/off. Branch 2 SV output SEU2 OFF=Branch2solenoidvalveoutputforcedOFF; status ON=Branch2solenoidvalveoutputforcedON. 924EHPNE4.01 - EHPN series humidifiers |71|Distributionrackuserinterface| 02/2024...
Page 72
Forcesthebranch6solenoidvalveoutputon/off. Branch 6 SV output SEU6 OFF=Branch6solenoidvalveoutputforcedOFF; status ON=Branch6solenoidvalveoutputforcedON. Forcesthebranch7solenoidvalveoutputon/off. Branch 7 SV output SEU7 OFF=Branch7solenoidvalveoutputforcedOFF; status ON=Branch7solenoidvalveoutputforcedON. Forcesthedehumidifier enable output on/off. Dehumidification OFF=Dehumidification enableoutputforcedOFF; enable output status ON=Dehumidification enable output forced ON. 924EHPNE4.01 - EHPN series humidifiers |72|Distributionrackuserinterface| 02/2024...
9.1 Before you start ....................74 9.2 First start-up instructions ..................74 9.3 Instructions for seasonal or long-term shut-down ........76 9.4 Starting up after a seasonal or long-term shut-down ........76 924EHPNE4.01 - EHPN series humidifiers | 73 | Power-up and start-up | 02/2024...
• Set the humidity setpoint SPto100%; NOTE:WiththeexceptionofsituationswherethesystemneedstobeinstalledbytheSupportCentre,whichwillcarryout the startup procedure. NOTE:ForVDI6022-1compliance,connectiontoventilationconsentismandatory.IncaseoflackofventilationintheAHU, the humidifier must be in the STOP state. NOTICE RISK OF ELECTRIC SHOCK, EXPLOSION OR FIRE Thefirstoilchangeshouldtakeplacebetween50...150hoursofoperation.Forsubsequentchanges,pleaserefertothe operating manual. 924EHPNE4.01 - EHPN series humidifiers | 75 | Power-up and start-up | 02/2024...
• Activatetheisolatorinstalledoutsidethehumidifierandopenthewatersupplysource; • PresstheON/OFFbuttonon the user interfacetostartthehumidifier; • RuntherackandAHUdisinfectioncycles; • Set the humidity setpoint SP to the value required for the application; • T hehumidifierrunsadistributionrackwashingcycleinordertokeepthehumidifierinagoodoperatingcondition. • Thehumidifierstartstoproducinghumidityonrequest. 924EHPNE4.01 - EHPN series humidifiers | 76 | Power-up and start-up | 02/2024...
The EHPNhigh-pressureadiabatichumidifierproducesmistbyconveyinghigh-pressurewater(80bar)inadistributionrack composedofnozzles.Microscopicholesinthenozzlesatomisethewaterintoafinemist,whichisabsorbedbytheairinthe duct. The EHPN series adiabatic humidification system regulates its operation according to the humidity request from the distributionrack(s).Whenthereisahumidityrequestfromthesensororexternalsignal(dependingontheconfiguration), eachrackopensoneormoresolenoidvalvessothatthenozzlesinstalledonthedistributionbranchesproducemist. The droplet separator (optional) is used to stop and water droplets that were not atomised before entering the duct.
The humidity production varies with the value read at analogue input S2,withthelogicexpressedinthegraphbelow,without exceeding parameter r6: 100% Line Description Production 10V= 100% Fig. 67. How proportional regulation works | CFG = PROP 924EHPNE4.01 - EHPN series humidifiers | 79 | Operation | 02/2024...
Page 80
The humidity production varies with the value read at analogue input S2,withthelogicexpressedinthegraphbelow,without exceeding parameter r6. 100% Line Description 100% Production Fig. 68. How regulation with the humidity sensor works | CFG = HUM 924EHPNE4.01 - EHPN series humidifiers | 80 | Operation | 02/2024...
Page 81
Humidity production behaves in the same way as for regulation with the humidity sensor (CFG=HUM),butthesecondsensor connected to analogue input S3stopssteamgeneration,dependingonthehumiditydelivery. The humidity limit activates when the humidity measured by sensor S3 exceeds SP2. 924EHPNE4.01 - EHPN series humidifiers | 81 | Operation | 02/2024...
Reverse osmosis system Inlet solenoid valve Pump unit Outlet solenoid valve Fig. 70. Rack management diagram Zone 1 Zone 2 Zone 3 Fig. 71. Rack management example Afterwashing,theEHPNresumesworkingaccordingthezonehumidityrequests. 924EHPNE4.01 - EHPN series humidifiers | 82 | Operation | 02/2024...
Page 83
• Outlet solenoid valve closed • Control unit activation signal enabled Activations Request Fig. 72. Rack management diagram Iftwobranchesareconfigured,thefirstbranchisalwaysactivatedwitharequestabovetheminimumproductionr5,while the second branch is activated when the request exceeds (r5+((r5+r6)/2). Ifthereisonlyonebranch,thisisalwaysactivewithahumidityrequestabovetheminimumr5. 924EHPNE4.01 - EHPN series humidifiers | 83 | Operation | 02/2024...
M16 Maintenance hours warning threshold for the reverse osmosis system. hx10 100...10000 M17 Maintenance hours warning threshold for the filters. hx10 100...10000 M18 Number of activations warning for the solenoid valves. nx1000 100...10000 924EHPNE4.01 - EHPN series humidifiers | 84 | Operation | 02/2024...
11. CONFIGURATION PARAMETERS Chapter content This chapter contains the following information: Subject Page 11.1 Regulation parameter table for the pump unit ..........87 11.2 Regulation parameter table for the distribution rack .........89 924EHPNE4.01 - EHPN series humidifiers |86|Configurationparameters| 02/2024...
Standard pressure setpoint hysteresis (SP4). 0...10 Minimum value for setting humidity setpoint. 0...r2 Maximum value for setting humidity setpoint. r1...100 Humidity proportional band. 0...50 Range to reach outlet pressure. 10...90 MAINTENANCE/ALARMS group Lowpumptemperaturealarmthreshold.Thehysteresisisfixedat2°C/°F. °C/°F 0.0...30.0 924EHPNE4.01 - EHPN series humidifiers |87|Configurationparameters| 02/2024...
M14 Maintenance hours warning threshold for the inlet solenoid valve. hx10 100...2000 1000 M15 Maintenance hours warning threshold for the outlet solenoid valve. hx10 100...2000 1000 M18 Number of activations warning for the solenoid valves. nx1000 100...10000 2000 924EHPNE4.01 - EHPN series humidifiers |89|Configurationparameters| 02/2024...
12.3 Modbus functions and registers TheModbusregistersforthedeviceareorganisedaroundthefourtypesofbasicdatareferenceindicatedabove,andthis type of data is further identified by the first number of the address. 924EHPNE4.01 - EHPN series humidifiers | 92 | Modbus RTU functions and resources | 02/2024...
In the other cases the value is always positive or zero. • DATA SIZE: Indicates the size in data bits: • DWORD =32bit • DOUBLE =32bit • WORD=16bit • Byte=8bit • The “n”bits=0...15bitdependingonthevalueof“n” 924EHPNE4.01 - EHPN series humidifiers | 93 | Modbus RTU functions and resources | 02/2024...
Page 98
0...65535 wALrack1 Rack1alarmAL16. 1314 WORD --- 0...65535 wALrack1 Rack1alarmAL17. 1314 WORD --- 0...65535 wALrack1 Rack1alarmAL18. 1314 WORD --- 0...65535 wALrack1 Rack1alarmAL20. 1314 WORD --- 0...65535 924EHPNE4.01 - EHPN series humidifiers | 98 | Modbus RTU functions and resources | 02/2024...
Page 99
1 BIT -32768 ... HumRack1 Rack1humiditysensorvalue. 1331 SHORT Y 32767 -32768 ... HumRack2 Rack2humiditysensorvalue. 1332 SHORT Y 32767 -32768 ... HumRack3 Rack3humiditysensorvalue. 1333 SHORT Y 32767 924EHPNE4.01 - EHPN series humidifiers | 99 | Modbus RTU functions and resources | 02/2024...
Page 100
SHORT Y 32767 -32768 ... LHumRack3 Rack3humiditylimitsensorvalue. 1336 SHORT Y 32767 MBS_SwEn On/Off command from BMS. 1922 R/W 1 BIT (*) Calculation of operating hours Operatinghours=(HIGHregisterx65536)+LOWregister 924EHPNE4.01 - EHPN series humidifiers | 100 | Modbus RTU functions and resources | 02/2024...
• AL23 displayed Alarm: HPN between distributionrackand AL23 and expansion board that manages • Alarm relay ON offline pump unit rackbranchEV4-EV5-EV6-EV7 • • Automatic reset • AL23 recorded in the log 924EHPNE4.01 - EHPN series humidifiers | 109 | Diagnostics | 02/2024...
Page 110
7 AL27 operation > M13 or number of • Alarm relay ON solenoid valve solenoid valve activations > M18 • HumidifierOFF maintenance • AL27 recorded in the log 924EHPNE4.01 - EHPN series humidifiers | 110 | Diagnostics | 02/2024...
This chapter contains the following information: Subject Page 14.1 Before you start ....................112 14.2 Opening the pump unit ..................114 14.3 Changing the oil cap ..................115 14.4 Changing oil ...................... 116 924EHPNE4.01 - EHPN series humidifiers | 111 | Maintenance | 02/2024...
14.1 Before you start EHPN series humidifiers are designed for operation with the water properties specified in the sub-section "WATER SPECIFICATIONS" ON PAGE 33. Using water with other properties and/or with a hardness level approaching the limit of 50 °f means that maintenance will be requiredmorefrequentlyandmuchgreaterattentionmustbepaidtothebiologicalrisk.
Page 113
• Intheeventofpoormaintenance/cleaningafterthehumidifierhasbeenshut-downforalongtime,microorganisms (including the bacteria that cause Legionellosis) may proliferate and be transferred into the air treatment system. • Thehumidifiermustbeusedproperlyandbemaintainedandcleanedproperlyatprescribedintervals,asdescribedinthe MAINTENANCE chapter. 924EHPNE4.01 - EHPN series humidifiers | 113 | Maintenance | 02/2024...
14.2 Opening the pump unit Forinstallersandmaintenancepersonnelonly. Toopenthepumpunit,undothe9hexagonheadscrewsintheunitasshowninthephotobelow,afterwhichyoucanremove the panel. Fig. 75. Opening the pump unit 924EHPNE4.01 - EHPN series humidifiers | 114 | Maintenance | 02/2024...
14.3 Changing the oil cap Duringinstallation,alwaysreplacetheredcapusedexclusivelyfortransportingthehumidifierwiththeyellowcapprovided. Fig. 76. Changing the oil cap 924EHPNE4.01 - EHPN series humidifiers | 115 | Maintenance | 02/2024...
Collect used oil in containers and dispose of it at the appropriate centres in accordance with the regulations in force. Never dispose of it in the environment. Fig. 78. Pump 924EHPNE4.01 - EHPN series humidifiers | 116 | Maintenance | 02/2024...
14.4.2 Checking the oil level Iftheoillevelisnotbetweenthedashedlines,addorremoveoilandcheckforleaks. Fig. 79. Checking the oil level NOTE:Takegreatcaretoavoiddamagingthetemperaturesensorfittedattheoutlettothepump. Refer to the pump manual for more information. 924EHPNE4.01 - EHPN series humidifiers | 117 | Maintenance | 02/2024...
15. SPARE PARTS Chapter content This chapter contains the following information: Subject Page 15.1 Pump unit ......................119 15.2 Distribution rack ....................120 924EHPNE4.01 - EHPN series humidifiers | 118 | SPARE PARTS | 02/2024...
16.3 Wiring diagram for EHPN single-branch humidifier Fig. 84. Wiring diagram for EHPN single-branch humidifier 924EHPNE4.01 - EHPN series humidifiers | 124 | Wiring diagrams | 02/2024...
Page 125
This page has been left blank on purpose. 924EHPNE4.01 - EHPN series humidifiers | 125 | 02/2024...
Page 126
This document and the solutions contained within it are the intellectual propertyofELSTEAM,safeguardedbytheItalianIndustrialPropertyCode (CPI).ELSTEAMforbidsthereproductionanddistribution,eveninpart,ofthe contents,unlessexpressauthorisationisobtaineddirectlyfromELSTEAM. Thecustomer(manufacturer,installerorenduser)assumesallresponsibility fordeviceconfiguration. ELSTEAM does not assume any responsibility for potential errors and reserves the right to make any changes, at any time, without the basic functionalandsafety-relatedfeaturesbeingaffected. MADE IN ITALY ELSTEAM S.r.l. ViaEnricoFermi496,21042,...