Water Fill Time; Purge Time; Heating Time; Ta Coefficient - Elsteam REH4 Installation, Use And Maintenance Manual

Air handling units resistors humidifier
Table of Contents

Advertisement

AHU Resistors Humidifier - REH

9.6 Water fill time

Set the time during which the inlet valve is open water. The time is in seconds, from 1 to 250.
Default 10".

9.7 Purge Time.

Set the purge time during which the drain system remains open to allow a small discharge of water.
The time is in seconds, from 1 to 250.
Default 1".

9.8 Heating time

Set the waiting time during which the water in the tank is heated by the passage of the current. The
time is in seconds, from 1 to 1200 (= 20min.).
Default 80".

9.9 TA coefficient.

Set the coefficient for the TA mounted in the humidifier. It is a number from 10 to 9999, modified in
steps of 10.
Default 750.

9.10 Level sensor

Set the type of level sensor connected. Can be chosen among:
HV Level switch (High Voltage). Input IN-DIG0
Contact with float on input IN-DIG1 (jumper JP2 must be closed):
a. N.C. = normally closed.
b. N.O. = normally open.
Default HV Level switch

9.11 Pressure threshold

2000Pa

9.12 Minimum 0-10V Input Calibration

This parameter allows varying the minimum threshold for intervention in the case of using an external
controller with different voltages from 0-10V.

9.13 Water change interval

It indicates the interval between complete changes of water in the kettle.
(Default 4h)
Elsteam S.r.l - via E. Fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007
21.2.EN
E-mail: info@elsteam.it Web: http://www.elsteam.com