10. DIAGNOSTICS

The table below lists alarms with corresponding solutions. Inhibiting alarms trigger the alarm relay.

10.1 Table of Alarms and Solutions

Description
Cause
No Water
No water in the boiler
alarm
No Production
No production or
alarm (#)
insufficient production
Insufficient or no water
Drain alarm
drainage
The measured
current exceeded
High Current
the nominal current
alarm
safety threshold for an
extended period
No Enabling
The activation contact
is not connected
Foamispresentor
electrodes are coated
Maximum level
in limescale and
alarm (*)
therefore worn out
oruninsulated,inlet
solenoidvalveleaking.
924VHE4.02 - VEH series humidifiers
Effects
Humidity production
inhibited
• # appears on the
display
• Indication only
• Alarm relay ON
• Indication only (if
partial drain)
• Humidity production
inhibited (if drain
completelyblocked)
Production inhibited
The humidifier does not
come on
• * appears on the
display
• Indication only
| 33 |
Solution
•  M akesuretheinletshut-offvalveisopen;
• Checkthesolenoidvalveconnections;
•  M akesurethesolenoidvalvefilterisnotblockedwith
deposits;
•  M akesurethesolenoidvalveisworkingproperlyand
replace it if necessary;
•  M akesurethesupplementaryfilterinstalledupstream
ofthehumidifierisnotblocked,replacethefilter
cartridge if necessary.
•  C heckthewaterinletsolenoidvalve(filtercloggedor
solenoid valve damaged);
•  C heckforanybreakagesorleaksinthehumidifiertank;
• Contact Elsteam customer service to replace the AT;
•  M akesuretheelectricalpowercablesareconnected
correctly.
•  C hecktheamountoflimescaleintheboilertankand
in the drain ducts for the machine and for the system
downstreamofthehumidifier;
• Manually clean the limescale from inside the hydraulic
unit,fillanddrainmanifoldandinthedrainducts;
•  M akesurethedrainpumpelectricalconnectionsare
correct;
•  M akesurethedrainpumpisworkingproperly;
•  M akesuretherearenoleaksfromtheinletsolenoid
valve.
• See Drain alarm Solution;
•  C heckhowthelimescaleisdepositedintheboilerand
makesuretherearejumpersbetweentheelectrodes;
• Clean it;
•  C heckthesupplywatertypeandmakesureit
correspondswiththespecificationsdescribedinthis
manual.
•  M akesurethereisaclosedcontactatterminals7and8;
•  M akesuretheelectroniccontrolisworking.
• Perform manual drain procedure to wash the hydraulic
unit and remove the foam;
• Perform maintenance and cleaning on the electrodes
andthetank,replacetheelectrodesifnecessary;
•  C heckforleaksfromtheoutletsolenoidvalveand
replace it if necessary.