Table 7-17 Error Counter; Table 7-18: Only Clear Error Counter For Channel 1 - Phoenix Contact CAPAROC Series User Manual

Table of Contents

Advertisement

CAPAROC system
Table 7-17
Error counter
Byte
Data
Data
offset
type
0
Byte
0 ... 255 = error counter channel 1
1
0 ... 255 = error counter channel 2
2
0 ... 255 = error counter channel 3
3
0 ... 255 = error counter channel 4
Example
50 / 66
PHOENIX CONTACT
7.2.2.4
Error counter (index 0004
This index can be used to read and reset the error counter for each channel. The read or
write command must be issued to the slot that corresponds to the module position in the
system. The subslot is always "1".
To reset the error counter for just one channel, the write command must be 4 bytes long.
The counter to be reset must include a "0" in the byte.
Clear error counter for channel 1 and retain error counter for channel 2:
Table 7-18
Only clear error counter for channel 1
Byte
Data
0
0
1
Any number from 1 ... 255
2
0
3
0
)
hex
Access
r/w
Default setting
0
109745_en_01