Input Process Data Of Caparoc E4 12-24Dc/1-10A - Phoenix Contact CAPAROC Series User Manual

Table of Contents

Advertisement

CAPAROC system
Table 7-7

Input process data of CAPAROC E4 12-24DC/1-10A

Byte
Data
Bit
offset
type
0
Byte
0
1
2
3
4
5 ... 7
1
Byte
0 ... 7
2
Byte
0 ... 7
3
Byte
0
1
2
3
4
5 ... 7
4
Byte
0 ... 7
5
Byte
0 ... 7
42 / 66
PHOENIX CONTACT
7.1.7

Input process data of CAPAROC E4 12-24DC/1-10A

A block of 3 bytes of input process data is transmitted for each channel on the device. The
CAPAROC E4 12-24DC/1-10A 4-channel circuit breaker module therefore has 12 bytes of
input process data.
Description
Switching status, channel 1
Warning 80% I
, channel 1
Nom
Overload, channel 1
Short circuit, channel 1
Defect, channel 1
Reserved
Set nominal current, channel 1
Flowing current, channel 1
Switching status, channel 2
Warning 80% I
, channel 2
Nom
Overload, channel 2
Short circuit, channel 2
Defect, channel 2
Reserved
Set nominal current, channel 2
Flowing current, channel 2
Value range
0 = channel is switched off
1 = channel is switched on
0 = warning inactive
1 = warning active
0 = no error
1 = overload shutdown
0 = no error
1 = short-circuit shutdown
0 = no defect
1 = hardware is defective
0
{1 ... 10} A
0 ... 255 (= 0 ... 25.5 A)
0 = channel is switched off
1 = channel is switched on
0 = warning inactive
1 = warning active
0 = no error
1 = overload shutdown
0 = no error
1 = short-circuit shutdown
0 = no defect
1 = hardware is defective
0
{1 ... 10} A
0 ... 255 (= 0 ... 25.5 A)