CAPAROC system
Table 7-8
Output process data of CAPAROC E4 12-24DC/1-10A
Byte
Data
Bit
offset
type
0
Byte
0
1 ... 6
7
1
Byte
0
1 ... 6
7
2
Byte
0
1 ... 6
7
3
Byte
0
1 ... 6
7
44 / 66
PHOENIX CONTACT
7.1.8
Output process data of CAPAROC E4 12-24DC/1-10A
The CAPAROC E4 12-24DC/1-10A 4-channel circuit breaker module has 4 bytes of output
process data, which is defined as follows:
Description
Switch channel 1
Reserved
Internal validity flag
Switch channel 2
Reserved
Internal validity flag
Switch channel 3
Reserved
Internal validity flag
Switch channel 4
Reserved
Internal validity flag
The internal validity flag prevents a non-initialized process data byte from causing the
unintentional shutdown of an output channel. The signal for switch-on or switch-off
must be applied for at least 1500 ms. Internally, only one validity flag is available per
module. The rest of the output process data for this module is also deemed valid as
soon as either of the two flags is set to "1".
Value range
0 = channel 1 off
1 = channel 1 on
0
1
0 = channel 2 off
1 = channel 2 on
0
1
0 = channel 3 off
1 = channel 3 on
0
1
0 = channel 4 off
1 = channel 4 on
0
1
109745_en_01