Input Process Data Of Caparoc E1 12-24Dc/1-10A; Output Process Data Of Caparoc E1 12-24Dc/1-10A - Phoenix Contact CAPAROC Series User Manual

Table of Contents

Advertisement

Table 7-3

Input process data of CAPAROC E1 12-24DC/1-10A

Byte
Data
Bit
offset
type
0
Byte
0
1
2
3
4
5 ... 7
1
Byte
0 ... 7
2
Byte
0 ... 7
Table 7-4

Output process data of CAPAROC E1 12-24DC/1-10A

Byte
Data
Bit
offset
type
0
Byte
0
1 ... 6
7
109745_en_01
7.1.3

Input process data of CAPAROC E1 12-24DC/1-10A

The CAPAROC E1 12-24DC/1-10A 1-channel circuit breaker module has 3 bytes of input
process data.
Description
Switching status, channel 1
Warning 80% I
, channel 1
Nom
Overload, channel 1
Short circuit, channel 1
Defect, channel 1
Reserved
Set nominal current, channel 1
Flowing current, channel 1
7.1.4

Output process data of CAPAROC E1 12-24DC/1-10A

The CAPAROC E1 12-24DC/1-10A 1-channel circuit breaker module has 1 byte of output
process data, which is defined as follows:
Description
Switch channel 1
Reserved
Internal validity flag
The internal validity flag prevents a non-initialized process data byte from causing the
unintentional shutdown of an output channel. The signal for switch-on or switch-off
must be applied for at least 1500 ms. Internally, only one validity flag is available per
module. The rest of the output process data for this module is also deemed valid as
soon as either of the two flags is set to "1".
Process, parameter, and diagnostic data
Value range
0 = channel is switched off
1 = channel is switched on
0 = warning inactive
1 = warning active
0 = no error
1 = overload shutdown
0 = no error
1 = short-circuit shutdown
0 = no defect
1 = hardware is defective
0
{1 ... 10} A
0 ... 255 (= 0 ... 25.5 A)
Value range
0 = channel 1 off
1 = channel 1 on
0
1
PHOENIX CONTACT
39 / 66