Converter 2 x 0...10 V / IO-Link DP1222 1 Preliminary note You will find instructions, technical data, approvals and further information using the QR code on the unit / packaging or at www.ifm.com. 1.1 Symbols used Requirement Instructions Reaction, result [...] Designation of keys, buttons or indications...
DP1222 Converter 2 x 0...10 V / IO-Link 2 Safety instructions • The unit described is a subcomponent for integration into a system. – The system architect is responsible for the safety of the system. – The system architect undertakes to perform a risk assessment and to create documentation in accordance with legal and normative requirements to be provided to the operator and user of the system.
The unit is not suited for environments with particular requirements on mechanical stability (e.g. shock/vibration). The unit is intended for indoor use only. u Observe the operating conditions (Ò Technical data at www.ifm.com).
DP1222 Converter 2 x 0...10 V / IO-Link 4 Function The unit provides the IO-Link process data according to the analogue input signals. The unit is designed for half-duplex communication. So the following options are possible: • Remote display: reading and displaying the current voltage value •...
Converter 2 x 0...10 V / IO-Link DP1222 4.2.2 Application example Fieldbus 0...10 V 24 V DC Fig. 2: Application example with IO-Link master Analogue sensor Converter 2 x 0...10 V / IO-Link Fully bidirectional IO-Link communication IO-Link master - Remote parameter setting: reading and changing the parameter setting Fieldbus (e.g.
DP1222 Converter 2 x 0...10 V / IO-Link 4.3.2 Window mode SP1: Switch-on point window SP1+H: Switch-off point SP1+H SP2-H SP2: Switch-on point window SP2-H: Switch-off point Fig. 5: NO (IO-Link parameter LoGc: high active) If the set voltage window is not complied with, this is signalled as “low” by a bit in the input process data.
Page 9
Converter 2 x 0...10 V / IO-Link DP1222 In operating mode 1, this function is not available.
DP1222 Converter 2 x 0...10 V / IO-Link 5 Installation u Install the unit so that the M12 connection parts and the unit are protected from mechanical stress such as shock and vibration. u If necessary, fix the unit with a clamp (use M4 screw or cable tie).
Converter 2 x 0...10 V / IO-Link DP1222 6 Electrical connection The device must be connected by a qualified electrician. Observe the national and international regulations for the installation of electrical equipment. Voltage supply according to EN 50178, SELV, PELV. CAUTION Input current is not limited.
DP1222 Converter 2 x 0...10 V / IO-Link 6.1 Mounting the connector To achieve the protection rating indicated in the data sheet, the following has to be observed: u Use IO-Link cable with IP class. u Connect the connector with the unit. The arrow indicates the position of the coding.
Converter 2 x 0...10 V / IO-Link DP1222 7 Operating and display elements LEDs 7.1 LEDs Colour Status Designation yellow Analogue value in the standard range: 0...100 % (0...10 V) flashing (2 Hz) Analogue value in the range: >100 % (>10 V)* Power green Voltage supply OK.
DP1222 Converter 2 x 0...10 V / IO-Link 8 Parameter setting During parameter setting the unit remains in the operating mode. It continues its functions with the existing parameters until the parameter setting has been completed. 8.1 Parameters via IO-Link 8.1.1 Application-specific tag Customer-specific application description, max.
Converter 2 x 0...10 V / IO-Link DP1222 • High active = status bit is set to “high” (if “High active” activated) • Low active = status bit is set to “low” (if “Low active” activated) In operating mode 1, this parameter is not available.
Converter 2 x 0...10 V / IO-Link DP1222 10 Troubleshooting Status Error Troubleshooting Check/correct the supply voltage. Ò Power flashing (5 Hz) Supply voltage too low Electrical connection No supply voltage Check/correct the supply voltage. Ò Electrical connection...
DP1222 Converter 2 x 0...10 V / IO-Link 11 Maintenance, repair and disposal Cleaning the unit: u Disconnect the unit from the voltage supply. u Clean the unit from dirt using a soft, chemically untreated and dry micro-fibre cloth. The operation of the unit is maintenance-free.
Converter 2 x 0...10 V / IO-Link DP1222 12 Factory settings Parameter Factory settings User settings mEAn Averaging 50 ms SSC1.ModE* Switch point mode Two point • Deactivated • Single point • Window • Two point SSC1.LoGc* Switch point logic Low active •...