Window Mode; Two Point Mode; Deactivated Mode - IFM DP1222 Operating Instructions Manual

Converter 2 x 0...10 v / io-link
Table of Contents

Advertisement

DP1222
4.3.2 Window mode
H
SSC
SP2-H
SP2
OFF
SP2
Fig. 5: NO (IO-Link parameter LoGc: high active)
If the set voltage window is not complied with, this is signalled as "low" by a bit in the input process
data.
H
SSC
SP2
SP2-H
ON
SP2
Fig. 6: NC (IO-Link parameter LoGc: low active)
If the set voltage window is not complied with, this is signalled as "high" by a bit in the input process
data.
In operating mode 1, this function is not available.
4.3.3 Two point mode
SSC
SP2
OFF
SP2
Fig. 7: NO (IO-Link parameter LoGc: no / high active)
If a set voltage is not reached, this is signalled as "low" by a bit in the input process data.
SSC
SP2
ON
SP2
Fig. 8: NC (IO-Link parameter LoGc: nc / low active)
If a set voltage is not reached, this is signalled as "high" by a bit in the input process data.
In operating mode 1, this function is not available.
4.3.4 Deactivated mode
NO (IO-Link parameter LoGc: high active)
The signal bit in the input process data is always signalled as "low".
NC (IO-Link parameter LoGc: low active)
The signal bit in the input process data is always signalled as "high".
8
H
SP1+H
SP1
ON
OFF
SP1
H
SP1
SP1+H
OFF
ON
SP1
H
SP1
ON
SP1
H
SP1
OFF
SP1
Converter 2 x 0...10 V / IO-Link
SP1:
Switch-on point window
SP1+H: Switch-off point
SP2:
Switch-on point window
SP2-H: Switch-off point
SP1:
Switch-off point window
SP1+H: Switch-on point
SP2:
Switch-off point window
SP2-H: Switch-on point
SP1:
Trigger point overvoltage
SP2:
Switch-off point
SP1:
Trigger point undervoltage
SP2:
Switch-on point