Start/Stop Mode - Pepperl+Fuchs K23-SSI/USB/25B-C Manual

Signal converter
Table of Contents

Advertisement

ERROR POLARITY
Defines the polarity of the error bit in the event of a fault
Value
0
1
Note
SSI values
To process SSI values, see Appendix

4.5 Start/Stop Mode

In this menu, the operation is defined as a start/stop interface converter.
INIT MODE
Managing or managed operation
Depending on the selected INIT MODE, different terminals must be used for the
init pulse.
Managing operation: Terminal X2—pins 1 and 2
Managed operation: Terminal X2—pins 5 and 6
Value Designation
0
1
SAMPLING TIME (ms)
Duration between two init pulses in milliseconds. Corresponds to the time after
which a new measurement is started and directly affects the reaction time of the
device.
Value
00.200
04.000
16.000
K23-SSI/USB/25B-C | O
Function
Bit is low in the event of a fault
Bit is high in the event of a fault
Function
PRIMARY
Managing operation: Init pulse is generated by the
device
SECONDARY
Managed operation: Init pulse is generated
externally
Function
Minimum measuring time
Default value
Maximum measuring time
S
OS6.0
PERATING
OFTWARE
35