Daikin DCC601A51 Installer's Reference Manual page 17

Intelligent tab controller
Hide thumbs Also See for DCC601A51:
Table of Contents

Advertisement

7
For each of these units, enter or confirm the following
information:
 The model name
 The serial number.
For the serial number, you can use the MFG.NO number as
displayed on the unit label. However, make sure no two units
connected to the intelligent Tab Controller have the same
serial number. If necessary, add a character to the serial
number to distinct them.
8
Click the lower Apply button to confirm these changes.
9
Confirm all entered data by clicking OK.
10 In the DIII Lines List window, click Indoor Units.
The Indoor Unit Setup window for this DIII-NET address will be
displayed.
11
Select the desired indoor unit from the list of indoor units.
12 For each selected indoor unit, enter or confirm the following
information:
 The model name
 The serial number
For the serial number, you can use the MFG.NO number as
displayed on the unit label. However, make sure no two units
connected to the intelligent Tab Controller have the same
serial number. If necessary, add a character to the serial
number to distinct them.
 The installation place
13 Click Apply to confirm the changes for this indoor unit.
14 Confirm all entered data by clicking OK.
15 In the DIII Lines List window, click OK to confirm all changes.
9.8.5.
Configuring the login information ([4] LC Information
Setup)
To connect to the cloud during the commissioning, you will need to
set up the login information. To do so, proceed as follows:
1
In the net commissioning tool, click LC Information Setup.
The following window will be displayed:
a
b
c
e
f
DCC601A51
intelligent Tab Controller
4P420109-1 – 2015.10
d
g
2
In this window, enter the following data:
Field
Explanation
Unique identification number of the intelligent
a
LC No
Tab Controller, as registered on the cloud.
b
DEV. Version
The current firmware version of the modules.
c
User ID
Your user id on the cloud.
d
Installation Date
Date of installation in yyyy/mm/dd format.
A short explanation of the installation location
e
Installation Place
(up to 20 characters).
Power line frequency. Choose between
f
Current Frequency
50 and 60 Hz.
Configures the AC Voltage for all outdoor
units.
AC Input Voltage
You can set this value for calculating the
g
Batch Setup
power consumption.
Choose one of the preset values, or enter a
custom value.
3
Click OK to confirm your settings.
9.8.6.
Commissioning the intelligent Tab Controller to the
cloud ([5] Commissioning)
Only when all unit information and user information is correctly
entered, you can complete the final step in commissioning the
intelligent Tab Controller. This step consists of sending all previously
entered information to the cloud.
To do so, proceed as follows:
1
In the net commissioning tool, click Commissioning.
The net commissioning tool will automatically check if there is
data to be transmitted.
2
In the File Transmission window, wait until File Transmission
Completed is displayed. If so, click OK.
3
If any information is missing, the Check Missing Data window
will display the reason why the file transmission failed.
If this happens, click OK. You will return to the main screen of
the net commissioning tool so you can correct where necessary.
4
If the file transmission was successful, the Check Missing Data
window will display Data Setup Completed.
When this happens, click OK to continue to the Commissioning
window.
5
In the Commissioning window, click Transmit to start sending
the setup to the cloud.
6
If any error occurs during the transmission, contact Daikin
support.
7
If the data transmission was successful, click Close and Exit the
net commissioning tool.
8
You can now use your browser to go to the cloud at:
http://cloud.daikineurope.com.
Alternatively, if an authentication code was entered, you can
also use the intelligent Tab Controller app on the Daikin-supplied
tablet (if applicable). If you did not do so, refer to
the function mode" on page
9.8.7.
Advanced settings
Next to the buttons necessary for the net commissioning, the net
commissioning tool has several Advanced Setting buttons.
These buttons are reserved for servicing or used in the case of
troubleshooting.
"10.5. Change
22.
Installer reference guide
16