Connecting The Power Supply To All Modules; Connecting The Lan Cable; Installation Of The Daikin-Supplied Router - Daikin DCC601A51 Installer's Reference Manual

Intelligent tab controller
Hide thumbs Also See for DCC601A51:
Table of Contents

Advertisement

7.2.

Connecting the power supply to all modules

For all wiring requirements, refer to
page
26.
Proceed as follows:
1
Connect the power supply to the three terminals, L (live),
N (neutral) and ground in the input section of the WAGO power
supply unit (PSU).
INFORMATION
Use a flat-head screwdriver to manipulate the WAGO PSU
cage clamp in such a way that the wires are fixed to the
power supply.
c
a Place the screwdriver in the upper clamp entry
and place it above the clamp.
b Push the clamp downwards by pivoting the
screwdriver in direction
clamp entry opens.
c Put the wire in the respective lower clamp
entry.
2
Connect the DC output of the WAGO PSU to the DC input of the
CPU module. Take the polarity of the wires into account.
3
Plug the A-type plug of the USB cable in the rightmost
USB socket on the CPU module. This socket is marked "I/O IF".
4
Plug the B-type plug of the USB cable in the B-type USB socket
on the I/O module.
5
Provide an earth connection to the
module, using one of the following two options:
 connect the terminal to the earth rail bar of the electrical
cabinet (if provided), or
 connect the terminal to the M3 earthing screw on the bottom
face of the WAGO PSU.
24 V DC
+ + - -
CPU
L
N
POWER
230 V AC
Installer reference guide
9
"15.8. Wiring requirements" on
b
a
'
'
b
, so that the lower
terminal of the CPU
I/O
CPU IF
I/O IF
USB
NOTICE
If you want to connect the earth wire to the WAGO PSU,
you can only use a stranded wire with a crimp-style
terminal on the tip of the wire.
Place the round crimp-style terminal on the wire up to the
insulated part and fasten the terminal with a Philips
screwdriver.
a
b
a Round crimp-style terminal
b Stranded conductor wire
6
Once all wiring has been completed and double-checked, turn
on the power supply.
CAUTION
The power supply is only guaranteed when the "DC OK"
LED on the WAGO PSU and the "CPU ALIVE" LEDs on
both the CPU module and the I/O module are blinking.
If one or more of the above LEDs are not lighting up, check
for faulty wiring.
INFORMATION
A new CPU module does not come with application
software installed. Therefore, the "ALARM" LED will be lit
red. This is as expected, see
table (CPU module)" on page
be installed during the commissioning phase, refer to
"9. Commissioning the intelligent Tab Controller setup" on
page
10.
7.3.

Connecting the LAN cable

For all wiring requirements, refer to
page
26.
Do not connect the LAN cable until you start commissioning the
intelligent Tab Controller. Otherwise, a network address conflict may
occur.
8.
Installation of the Daikin-supplied
router
For information on the installation, refer to the manual provided with
the Daikin-supplied router. For information on when to use the
Daikin-supplied router, refer to
intelligent Tab Controller solution" on page
The following table gives an overview of the most relevant
information.
Requirement
Default WiFi name (SSID)
Default WiFi password (access
key)
Router configuration URL
Router configuration password
"LED status and operation
6. Application software will
"15.8. Wiring requirements" on
"4.4. Additional components in the
3.
Information
ASUS
To be found on the sticker at the back
of the router.
Use one of the following:
http://192.168.1.1
http://router.asus.com
Not set. You will set this when you start
the router's "Quick internet setup"
feature.
DCC601A51
intelligent Tab Controller
4P420109-1 – 2015.10

Advertisement

Table of Contents
loading

Table of Contents