Kohler 24RCL Manual page 72

Residential/light commercial generator sets
Hide thumbs Also See for 24RCL:
Table of Contents

Advertisement

Status Message
Minor Fault
NFPA Alarm
NormSrcUnavl (RXT required)
Rmt StartCmd
Run Btn Ack
(Run Button Acknowledged)
Start Delay
System Ready
VSpdStartCmd
(Variable Speed Start Command
Issued)
Load Shed 1 Status Info
Load Shed 2 Status Info
Load Shed 3 Status Info
Load Shed 4 Status Info
Load Shed 5 Status Info
Load Shed 6 Status Info
* Programmable Interface Module (PIM) required
[ Load management device required (LCM, load shed kit, or RXT with combined interface/ load management board).
Figure 5-3 Status Messages Displayed on the RDC2 Controller
72
Section 5 Troubleshooting
Action
Notice
The digital output for Minor Fault (PIM) is
active (contacts closed), indicating either
the digital input for Ground Fault
Indicator Warning (PIM) is active (low) or
the controller detected Low Cranking
Voltage.
Notice
The digital output for NFPA Alarm Active
(PIM) is active (contacts closed),
indicating that at least one of the NFPA
faults or warnings is active.
Notice
The normal power source (source1) is
disconnected, unavailable or
unacceptable.
Notice
The controller has received a remote
start signal while the master switch is in
AUTO, and will go to normal running.
Notice
The RUN button on the controller has
been pushed.
Notice
The digital output for Engine Start Delay
(PIM) is active (contacts closed),
indicating the engine is in between active
cranking cycles.
Notice
The digital output for System Ready
(PIM) is active (contacts closed),
indicating the generator has no active
faults or warnings.
Notice
A diagnostic exercise request has been
received by the controller.
Notice
The digital output for LoadPriority1Shed
[
is active (contacts closed), indicating the
1st priority load shed 1st priority load
shed (load management device) has
been activated.
Notice
The digital output for LoadPriority2Shed
[
is active (contacts closed), indicating the
2nd priority load shed 1st priority load
shed (load management device) has
been activated.
Notice
The digital output for LoadPriority3Shed
[
is active (contacts closed), indicating the
3rd priority load shed 1st priority load
shed (load management device) has
been activated.
Notice
The digital output for LoadPriority4Shed
[
is active (contacts closed), indicating the
4th priority load shed 1st priority load
shed (load management device) has
been activated.
Notice
The digital output for LoadPriority5Shed
[
is active (contacts closed), indicating the
5th priority load shed 1st priority load
shed (load management device) has
been activated.
Notice
The digital output for LoadPriority6Shed
[
is active (contacts closed), indicating the
6th priority load shed 1st priority load
shed (load management device) has
been activated.
Description/ Comments
Check
Check customer equipment
connected to the PIM module.
Check cranking battery
condition.
Check for faults and
troubleshoot any/all fault
conditions individually.
Check for utility source power
outage. Check wiring and
connections to the ATS.
Verify remote start signal.
Consult ATS operations
manual for cause of generator
start.
NA
NA
NA
Check for a remote exercise
command from OnCue.
Remove loads as required.
Check building wiring for
proper load distribution.
Check engine fuel supply.
Remove loads as required.
Check building wiring for
proper load distribution.
Check engine fuel supply.
Remove loads as required.
Check building wiring for
proper load distribution.
Check engine fuel supply.
Remove loads as required.
Check building wiring for
proper load distribution.
Check engine fuel supply.
Remove loads as required.
Check building wiring for
proper load distribution.
Check engine fuel supply.
Remove loads as required.
Check building wiring for
proper load distribution.
Check engine fuel supply.
TP-6907 5/16