Kohler 24RCL Manual page 69

Residential/light commercial generator sets
Hide thumbs Also See for 24RCL:
Table of Contents

Advertisement

Fault Message
OB1 CommLoss
(PIM, load management device,
or RXT)
OB2 CommLoss
(PIM, load management device,
or RXT)
OB3 CommLoss
(PIM, load management device,
or RXT)
OB4 CommLoss
(PIM, load management device,
or RXT)
Oil Pressure Low Shutdwn
Oil Sens Hi Warning
Oil Sens Lo Warning
Over Crank Shutdwn
PrimLoopOpn Warning
PrimLoopSht Warning
RBUS ComError Warning
Spd Sens Flt Shutdwn
(Speed sensor fault)
Volts L1-L2 High Shutdwn
Volts L1-L2 Low Shutdwn
* Programmable Interface Module (PIM) required
[ Applies during exercise runs and normal operation.
TP-6907 5/16
Action
Warning
Communications with option board #1
has been lost.
Warning
Communications with option board #2
has been lost.
Warning
Communications with option board #3
has been lost.
Warning
Communications with option board #4
has been lost.
Shutdown
The ECM shutdown the engine and
reported low oil pressure as the fault.
Warning
The ECM reported a high voltage error
for the oil pressure sensor.
Warning
The ECM reported a low voltage error
for the oil pressure sensor.
Shutdown
The controller shut down the generator,
and ceased cranking, because the
engine was not successfully started
after the completion of the last of the
crank cycles setting delay 15 seconds.
Warning
Ignition coil 1 voltage is below normal or
there is an open circuit.
Warning
Ignition coil 1 voltage is abnormal.
Warning
The controller has lost communications
with a PIM, or load management device
that had previously been
communicating properly.
Shutdown
The controller, or the ECM, shutdown
the generator because the speed signal
was lost.
Shutdown
The controller shut down the generator
[
because the voltage measured from
Phase A to Phase B exceeded the high
limit for a time greater than the delay
setting 2 seconds.
Shutdown
The controller shut down the generator
[
because the voltage measured from
Phase A to Phase B was greater 5% of
rated, but less than the low voltage
setting for a time greater than the delay
setting 10 seconds.
Description/ Comments
Check
Check RBUS wiring to
inoperative option board.
Check RBUS wiring to
inoperative option board.
Check RBUS wiring to
inoperative option board.
Check RBUS wiring to
inoperative option board.
Check the oil level and add oil
if low.
Check the oil pressure sensor
and wiring.
Check the oil level and add oil
if low.
Check the oil pressure sensor
and wiring.
Check for oil leaks.
Check the oil level and add oil
if low.
Check the oil pressure sensor
and wiring.
Check fuel supply. Check
cranking circuit. Check
cranking battery.
Troubleshoot engine; see
Engine Service Manuals.
Check the battery voltage.
Check the ignition wires for
shorts.
Check the battery voltage.
Check the ignition wires for
shorts.
Check connection to the PIM,
or load management device.
Check speed sensor and
circuitry to ECM.
Troubleshoot alternator; see
alternator service manual.
Troubleshoot alternator; see
alternator service manual.
Section 5 Troubleshooting
69