F113-A
FLOW RATE INDICATOR / TOTALIZER
with high / low flowrate alarms
Signal input flowmeter: (0)4-20mA
Signal outputs: (0)4-20mA ref. flow rate and pulse ref. total.
Alarm outputs: maximum four flowrate alarms
Options: Intrinsically safe, Modbus communication, external reset and
backlight.
F-Series - Field mounted indicators for safe and hazardous areas.
More info: www.fluidwell.com/fseries

Advertisement

Table of Contents
loading

Summary of Contents for Fluidwell F113-A

  • Page 1 Signal input flowmeter: (0)4-20mA Signal outputs: (0)4-20mA ref. flow rate and pulse ref. total. Alarm outputs: maximum four flowrate alarms Options: Intrinsically safe, Modbus communication, external reset and backlight. F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries...
  • Page 2: Safety Instructions

    This unit must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility). ▪ Do connect a proper grounding to the metal enclosure as indicated if the F113-A has an incoming power line which carries a 115-230V AC. The Protective Earth (PE) wire may never be disconnected or removed.
  • Page 3: About The Manual

    This manual describes the standard unit as well as the available options. For additional information, please contact your supplier. A hazardous situation may occur if the F113-A is not used for the purpose it was designed for or is used incorrectly. Please carefully note the information in this operating manual indicated by the pictograms: A "warning !"...
  • Page 4: Table Of Contents

    2.1. Control panel ....................... 6 2.2. Operator information and functions................6 Configuration ......................8 3.1. How to program the F113-A ..................8 3.1.1. Setup menu - Settings ....................10 Explanation of SETUP-menu 1 – Total ..............11 3.1.2. 3.1.3. Explanation of SETUP-menu 2 - Flow rate ............... 11 3.1.4.
  • Page 5: Introduction

    Fig. 1: Typical application Configuration The F113-A is designed for use in many types of applications. For that reason, a setup menu is available to program the F113-A according to your specific requirements. The setup includes several important features, such as span, engineering units, signal selection, power management (to extend battery life-time), etc.
  • Page 6: Operational

    • Take careful notice of the "Safety rules, instructions and precautionary measures" in the front of this manual. This chapter describes the daily use of the F113-A. This instruction is meant for users / operators. 2.1. CONTROL PANEL The control panel has three keys. The available keys are: Fig.
  • Page 7 ▪ How to program the alarm thresholds The F113-A can give an alarm message on the display. When set to on, at the same time, the digital outputs can give a signal for processing by an external device. Note that it is also possible to set or change the alarm thresholds from the setup menu.
  • Page 8: Configuration

    How to enter the setup menu When the setup menu is protected by a password, the F113-A asks for a password to access the setup menu. When in the operator mode, press and hold the PROG/ENTER key for 7 seconds to access the setup menu.
  • Page 9 The SELECT/▲ key and the CLEAR/► key are used for navigation. The explanation assumes that you are in the submenu TOTAL. When you are: • in the first setting and you navigate to the previous setting, the F113-A goes back to the related main menu.
  • Page 10: Setup Menu - Settings

    0.001 - 9 amount 0.001 - 9999999 COMMUNICATION speed 1200; 2400; 4800; 9600 address 1 - 247 mode bus-rtu; bus-asc; off DATABITS 8 bits; 7 bits PARITY none; even; odd OTHERS model F113-A software version nn:nn:nn serial no. nnnnnnn FW_F113A_v1901_02_EN.docx...
  • Page 11: Explanation Of Setup-Menu 1 - Total

    Page 11 password 0000 - 9999 tag-nr 0000000 - 9999999 EXPLANATION OF SETUP-MENU 1 – TOTAL 3.1.2. This setting is used to select the engineering unit for the indication of the total, the UNIT accumulated total and the pulse output. When you change the engineering unit , you must recalculate and reprogram the span for the (accumulated) total.
  • Page 12: Explanation Of Setup Menu 3 - Alarm

    3.1.4. EXPLANATION OF SETUP MENU 3 - ALARM These settings determine how the flow rate is monitored and how the F113-A will process the alarm conditions. For the setup of the configurable outputs, refer to setup menu: Relays. FLOWZERO When the flow rate is zero, then it is possible to ignore or disable the flow rate monitoring.
  • Page 13: Explanation Of Setup-Menu 5 - Power Management

    When used with the internal battery option (type PB/PC), the user can expect reliable measurement over a long period of time. The F113-A has several smart power management functions to extend the battery life time significantly. Two of these functions can be set.
  • Page 14: Explanation Of Setup Menu 7 - Analog

    Page 14 XAMPLE UNCTION EQUIRED EQUIRED OUTPUT SETUP SETUP SETUP 13/24) interpolation 450 L/min 25 L/min 25/450 x 100%=5.5% 16mA x 5.5% + 4mA = 4.88mA square root 450 L/min 25 L/min (25/450) x 100%=0.3% 16mA x 0.3% + 4mA = 4.05mA CALIB-LO This setting is used to calibrate the input value for (0)4mA as the signal from the flowmeter might not be exact 4.0 mA (or 0.0 mA) at flow rate...
  • Page 15: Explanation Of Setup Menu 8 - Relays

    Page 15 TUNE-MIN The (0)4mA or 0V value can be tuned precisely with this setting. The initial minimum analog output value is (0)4mA or 0V. However, this value might differ slightly due to ambient influences such as temperature for example. Before tuning the signal, be sure that the analog signal is not being used for any application! After pressing PROG, the current will be about 4mA (0mA or 0V).
  • Page 16: Explanation Of Setup-Menu 9 - Communication (Option)

    Only persons who know the pin code can access the setup menu. The pin code 0000 disables the pin code to allow for access by any person. TAG-NR This setting is used to set a tag number for the F113-A . FW_F113A_v1901_02_EN.docx...
  • Page 17: Installation

    When used in very cold surroundings or varying climatic conditions, inside the instrument case, take the necessary precautions against moisture. Mount the F113-A onto a solid structure to avoid vibrations.. For use in Safe and Hazardous Areas (or Locations), the following conditions apply: Relative humidity: <...
  • Page 18: Dimensions- Enclosure

    Page 18 4.3. DIMENSIONS- ENCLOSURE Aluminum and stainless enclosures (where “H” turns to “HS” for stainless, e.g. HA → HSA): 75 mm (2.95") 112 mm (4.40") 130 mm (5.12") 12mm 12mm 30mm 30mm 24mm 24mm M20 x 1,5 6 x M12 36mm 36mm 25mm...
  • Page 19 Page 19 75 mm (2.95") 112 mm (4.40") 130 mm (5.12") HK back box: (flat bottom) 75 mm (2.95") 118 mm (4.65”) 25mm 25mm D=20mm D=20mm 12mm 12mm 30mm 30mm 24mm 24mm D=12mm D=16mm D=16mm D=20mm 36mm 36mm 0.12” 0.12” D=22mm (0.866") 3x D=22mm (0.866”) 29.1 mm (1.15”)
  • Page 20: Installing The Hardware

    4.4.1. GENERAL INSTALLATION GUIDELINES • The F113-A that came with a power module type PM; 110V-230V AC or type PD/PF with an option OR (the relays can handle 110V-230V AC) shall be connected to the Protective Earth (PE) stud which is installed in the metal back panel. The metal front panel is connected to the Protective Earth by the mounting screws and serrated washers.
  • Page 21: Protective Earth (Pe) Connections

    Metal enclosure When the F113-A is supplied with a metal enclosure (aluminum or stainless steel), the enclosure must be grounded in accordance with national and local electrical codes. To ground the field mounted unit, the PE conductor must be connected to the PE stud which is located in the metal back cover, as indicated in the image below.
  • Page 22: Aluminum Enclosure - Panel Mounted

    Page 22 The PE connection in the metal back panel is made with a serrated washer, a terminal, a washer and a screw. The PE connection to the metal cover is made with the serrated washers and the mounting screws. Type PM (110-230V AC) Type OR (8-24V AC) Type OR (8-30V DC)
  • Page 23: Plastic (Grp) Enclosure

    Page 23 4.4.5. PLASTIC (GRP) ENCLOSURE The PE connection The F113-A in a GRP enclosure meets the requirements of class 2 (double insulated). Therefore the incoming PE wire is terminated with an insulating end cap. Type PM (110-230V AC) Type OR (8-24V AC) Type OR (8-30V DC) FW_F113A_v1901_02_EN.docx...
  • Page 24: Terminal Connectors

    Page 24 4.4.6. TERMINAL CONNECTORS The following paragraphs describe the terminal connections and configurations that are specific for types of supply PM, PF, PD and PX in combination with types OA, OT and OR. For type PD-OS (4 mechanical relay outputs), please consult the addendum to this manual specific for this type: ‘F1xx-A-PD-OS Addendum / Installation Guide’...
  • Page 25 5. Close the F113-A . Risk of electrocution - High voltage! Make sure, all the leads to the terminals are disconnected from the F113-A and NEVER connect the mains power supply to the unit when the protection cover has been removed!
  • Page 26 Page 26 Type OA An active 24V DC signal flow rate alarm output or pulse output is available with this option. Max. driving capacity 50mA@24V per output. (Requires power supply type PD/PF/PM). Fig. 10: Terminal connections - Active output (typical) Type OR: A mechanical relay output flow rate alarm output or pulse output is available with this option.
  • Page 27 Page 27 Terminal 07-08; basic POWER SUPPLY - type AP - output loop powered: Connect an external power supply of 8-30VDC to these terminals or a 4-20mA loop. Do connect the "-" to terminal 7 and the "+" to terminal 8. When power is applied to these terminals, the (optional) internal battery will be disabled / enabled automatically to extend the battery life time.
  • Page 28 Fig. 17: Terminal connections - Active 0-10V analog output (typical) Terminal 09-11: Type A – Flowmeter input (general) The F113-A requires a (0)4-20mA flowmeter signal which will be processed 4 times a second with a 16 bits accuracy. The input is not isolated.
  • Page 29 Page 29 Fig. 19: Terminal connections - Analog signal input – Loop-powered (typical) Terminal 12-13: Type IB – external reset (option): With this function the total can be reset to zero with an external switch. The Total resets only when the switch opens.
  • Page 30 Page 30 Terminal 26-31: type CB / CH / CI / CT - communication RS232 / RS485 / TTL (option) For connections, refer to figure: Overview of terminal connectors - Standard configuration and options. Full serial communications and computer control in accordance with RS232 (length of cable max. 15 meters) or RS485 (length of cable max.
  • Page 31: Intrinsically Safe Applications

    Please note • Certificates, safety values, control drawing and declaration of conformity can be found in the document named: “Fluidwell F1..-..-XI - Documentation for Intrinsic safety”. • When installing this device in hazardous areas, the wiring and installation must comply with the appropriate installation standards for your industry.
  • Page 32 Page 32 Serial number and year of production This information can be looked-up in the setup menu: Others. Fig. 23: Example serial number (typical) Label information pulse input type – F1xx-..-..-XI (inside and outside the enclosure) Fig. 24: Label information - Intrinsically safe application (typical) FW_F113A_v1901_02_EN.docx...
  • Page 33: Terminal Connectors Intrinsically Safe Applications

    3 and 4 and/or terminals 5 and 6; the maximum values for any of those circuits are those as defined for group IIB/IIIC. Terminal connectors F113-A-XI: For intrinsically safe applications, consult the safety values in the certificate.
  • Page 34 5. Close the F113-A . Risk of electrocution - High voltage! Make sure, all the leads to the terminals are disconnected from the F113-A and NEVER connect the mains power supply to the unit when the protection cover has been removed! Type PD-XI Power supply in: 16-30V DC / max.
  • Page 35: Configuration Examples Intrinsically Safe Applications

    Page 35 5.3. CONFIGURATION EXAMPLES INTRINSICALLY SAFE APPLICATIONS Fig. 28: F113-A-AP-CT-IB-OT-(PC)-(PD)-XI - Battery powered - IIB/IIC – IIIC FW_F113A_v1901_02_EN.docx...
  • Page 36 Page 36 Fig. 29: F113-A-AP-(CT)-IB-OT-PD-XI - External power supply - IIC FW_F113A_v1901_02_EN.docx...
  • Page 37: Battery Replacement Instructions

    Page 37 BATTERY REPLACEMENT INSTRUCTIONS 5.4.1. SAFETY INSTRUCTIONS • Handle the battery with care. A mistreated battery can become unsafe. Unsafe batteries can cause (serious) injury to persons. • Only use batteries which are certified for use in hazardous areas. The use of standard batteries in hazardous area's is not safe and prohibited.
  • Page 38: Maintenance

    Repairs should only be carried out by the manufacturer or his authorized agent. 6.3. REPAIR POLICY If you have any problem with your Fluidwell product and you wish to repair it, please follow the procedure below: a. Obtain a Return Material Authorization (RMA) from your supplier or distributor Together with the RMA, you need to complete a repair form to submit detailed information about the problem.
  • Page 39: Appendix A: Technical Specification

    Page 39 APPENDIX A: TECHNICAL SPECIFICATION GENERAL Display Type High intensity reflective numeric and alphanumeric LCD, UV-resistant. Digits Seven 17mm (0.67") and eleven 8mm (0.31"). Various symbols and measuring units. Refresh rate User definable: 8 times/sec - 30 secs. Type ZB LCD with LED backlight.
  • Page 40 Page 40 Sensor excitation Type PB / PC / PX 3V DC for low power pulse signals and 1.2V DC for coil pick-up. Type PD 1.2; 3; 8.2; 12; 24V DC - max. 50mA@24V DC Type PD-XI Intrinsically ally safe: Pulse signals: 1.2; 3; 8.2 - max. 7mA@8.2V DC. Type PF / PM 1.2;...
  • Page 41 Page 41 (requires type AP, OR and PD). Type OT Three passive transistor outputs - not isolated. Load: max. 50V DC - 300mA Communication option Protocol bus-rtu; bus-asc Speed 1200; 2400; 4800; 9600 Addressing 1 - 247 Type CB RS232 Type CH RS485 2-wire Type CI...
  • Page 42: Appendix B: Problem Solving

    Page 42 APPENDIX B: PROBLEM SOLVING In this appendix, several problems are included that can occur when the F113-A is going to be installed or while it is in operation. Analog output does not function properly: Check: ▪ is the analog output enabled? ▪...
  • Page 43: Appendix C: Communication Variables

    Page 43 APPENDIX C: COMMUNICATION VARIABLES GENERAL The product is fitted with the Modbus communication protocol and can be equipped with various physical interfaces like RS485 and RS232 (please see device datasheet for available options). The tables below show the various variables that can be accessed through the communication. Currently, the function codes supported are: •...
  • Page 44 Page 44 Setup variables REGISTER VARIABLE TYPE VALUE / REMARKS ADDRESS TOTAL REGISTERS [d] 32 40033 unit uint16 0=none 3=kg 6= US GAL [h] 0x020 4= lb 7=bbl 2= m 5=gal [d] 33 40034 decimals uint16 0…3 [h] 0x021 [d] 34 40035 span uint32 1...9999999...
  • Page 45 Page 45 REGISTER VARIABLE TYPE VALUE / REMARKS ADDRESS FLOWMETER REGISTERS [d] 98 40099 formula uint16 0=linear 1=square root [h] 0x062 [d] 99 40100 filter uint16 1...99 [h] 0x063 [d] 100 40101 cut-off uint16 0...999 [h] 0x064 Representation: 0.0 – 99.9% [d] 102 40103 calibrate low...
  • Page 46 Page 46 REGISTER VARIABLE TYPE VALUE / REMARKS ADDRESS REGISTERS [d] 173 40174 model number uint16 0…9999 [h] 0x0AD [d] 160 40161 model suffix char Representation: ASCII character [h] 0x0A0 [d] 162 40163 firmware version uint32 0…999999 [h] 0x0A2 Representation: nn:nn:nn [d] 165 40166 serial no...
  • Page 47: Appendix D: Declaration Of Conformity

    Page 47 APPENDIX D: DECLARATION OF CONFORMITY FW_F113A_v1901_02_EN.docx...
  • Page 48: Index Of This Manual

    Fig. 26: Terminal connections - Intrinsically safe floating 4-20mA analog output (typical) ....34 Fig. 27: Sensor supply voltage - Switch setting (Intrinsically safe) ............ 34 Fig. 28: F113-A-AP-CT-IB-OT-(PC)-(PD)-XI - Battery powered - IIB/IIC – IIIC ........35 Fig. 29: F113-A-AP-(CT)-IB-OT-PD-XI - External power supply - IIC ..........36...
  • Page 49 Page 49 OTES …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………… FW_F113A_v1901_02_EN.docx...
  • Page 50 Page 50 LIST OF CONFIGURATION SETTINGS SETTING DEFAULT DATE : DATE : 1 - TOTAL Enter your settings here 11 unit 12 decimals 0000000 13 span /sec /sec 001600 /sec 14 decs span 2 - FLOW RATE 21 unit 22 time unit /sec 23 decimals 0000000...
  • Page 51 Page 51 95 parity none A - OTHERS A1 model F113-A A2 software version A3 serial no. A4 password 0000 A5 tag-nr 0000000 FW_F113A_v1901_02_EN.docx...
  • Page 52 Page 52 Fluidwell B.V. PO box 6 Voltaweg 23 Website: www.fluidwell.com FW_F113A_v1901_02_EN.docx 5460 AA Veghel 5466 AZ Veghel Find your nearest representative: www.fluidwell.com/representatives the Netherlands the Netherlands © 2021 Fluidwell B.V.: FW_F113A_v1901_01_EN.docx...