Troubleshooting - Carrier Infinity 48XL Installation Instructions Manual

15 seer single packaged air condotioner and gas furnace system with puron (r-410a) refrigerant
Hide thumbs Also See for Infinity 48XL:
Table of Contents

Advertisement

- Defrost
operation
- Low ambient
cooling
- Crankcase
heater operation
- Compressor
external
protection
- Pressure
switch monitoring
(refrigerant)
- Time delays
FURNACE
BOARD
The furnace
board controls
the following
functions:
- Indoor blower
operation
- Gas valve
- Inducer
motor
- Remote
sparker
module
- Pressure
switch monitoring
(gas)
SYSTEMS
COMMUNICATION
FAILURE
If communication
with the Infinity
Control
is lost with the
UI, the
controls
will flash the appropriate
fault codes.
Check the wiring
to
the UI, indoor
and outdoor
units.
MODEL
PLUG
The HP/AC
control
board must have a valid model
plug to operate.
If a valid
model
plug is not detected,
it will not operate
and the
control will flash the appropriate
fault code, shown
in Table 5.
PRESSURE
SWITCH
PROTECTION-REFRIGERANT
The unit is equipped
with high-
and low-pressure
switches.
If the
control
senses the opening
of a high-
or low-pressure
switch,
it
will respond
as follows:
1. De-energize
the compressor
contactor
(HPS1
& LPS) or the
compressor
solenoid
contactor
(HPS2).
2. Keep the outdoor
fan operating
for 15 minutes.
3. Display
the appropriate
fault codes.
4. After a 15 minute
delay, if there is still a call for cooling
and
the
LPS
or HPS
is reset,
the
compressor
contactor
is
energized.
5. If LPS or HPS has not closed
after a 15 minute
delay, the
outdoor
fan is turned off. If the open switch
closes anytime
after the 15-minute
delay, then resume
operation
with a call
for cooling.
6. If LPS or HPS trips 3 consecutive
cycles, the unit operation
is locked out for 4 hours.
7. In the event of a high-pressure
switch
trip or high pressure
lockout,
check the refrigerant
charge,
outdoor
fan operation
and outdoor
coil for airflow
restrictions.
8. In the event of a low-pressure
switch
trip or low pressure
lockout,
check the refrigerant
charge and indoor
airflow.
CONTROL
FAULT
If the HP/AC
control
board
has failed, the control
will flash the
appropriate
fault code
(See TaMe 5). The control board should
be
replaced.
BROWN
OUT PROTECTION
If the line
voltage
is less than
187v
for at least 4 seconds,
the
appropriate
compressor
contactor
and fan relay are de-energized.
Compressor
and fan operation
are not allowed
until voltage
is a
minimum
of 190v.
The control
will flash
the appropriate
fault
code
(See Table 5).
230V LINE (POWER
DISCONNECT)
DETECTION
If there is no 230v
at the compressor
contactor
when
the unit is
powered
and cooling
demand
exists, the appropriate
error code is
displayed.
Verify that the disconnect
is closed
and 230v wiring
is
connected
to the unit.
COMPRESSOR
VOLTAGE
SENSING
The control
board
input
terminals
VS and L2 (See
Fig. 18) are
used
to detect
compressor
voltage
status,
and
alert the
user of
potential
problems.
The control
continuously
monitors
the high
voltage
on the run
capacitor
of the compressor
motor.
Voltage
should
be present
any time the compressor
contactor
is energized,
and
voltage
should
not
be
present
when
the
contactor
is
de-energized.
CONTACTOR
SHORTED
DETECTION
If there is compressor
voltage
sensed when there is no demand
for
compressor
operation,
the contactor
may be stuck closed or there is
a wiring
error.
The control
will flash the appropriate
fault code.
COMPRESSOR
THERMAL
CUTOUT
If the control
senses
the compressor
voltage
after start-up,
and is
then
absent
for 10 consecutive
seconds
while
cooling
demand
exists, the thermal
protector
is open.
The control
de-energizes
the
compressor
contactor
for 15 minutes,
but continues
to operate
the
outdoor
fan.
The control
Status
LED
will flash
the appropriate
code shown
in Table 5.
After 15 minutes,
with
a call for low or
high
stage cooling,
the compressor
contactor
is energized.
If the
thermal
protector
has not re-set,
the outdoor
fan is turned
off.
If
the
call
for
cooling
continues,
the
control
will
energize
the
compressor
contactor
every
15 minutes.
If the thermal
protector
closes
(at the next 15 minute
interval),
check the unit will resume
operation.
If the thermal
cutout
trips for three consecutive
cycles,
then unit
operation
is locked
out for 4 hours and the appropriate
fault code is
displayed.
NO 230V AT COMPRESSOR
If the
compressor
voltage
is not
sensed
when
the compressor
should
be starting,
the contactor
may be stuck open
or there is a
wiring
error.
The control
will flash
the appropriate
fault code.
Check the contactor
and control box wiring.
TROUBLESHOOTING
UNIT
FOR
PROPER
SWITCHING
BETWEEN
LOW & HIGH
STAGES
Check the suction
pressures
at the service valves.
Suction
pressure
should
be reduced
by 3-10%
when
switching
from
low to high
capacity.
NOTE:
The liquid
pressures
are very
similar
between
low and
high
stage
operation,
so liquid
pressure
should
not be used
for
troubleshooting.
Compressor
current should
increase
20-45%
when
switching
from
low to high stage.
The compressor
solenoid,
when
energized
in
high stage, should measure
24vac.
COMPRESSOR
INTERNAL
RELIEF
The compressor
is protected
by an internal
pressure
relief (IPR)
which
relieves
discharge
gas
into
compressor
shell
when
differential
between
suction
and discharge
pressures
exceeds
550 -
625 psi. The compressor
is also protected
by an internal
overload
attached
to motor windings.
TEMPERATURE
THERMISTORS
Thermistors
are electronic
devices which
sense temperature.
As the
temperature
increases,
the
resistance
decreases.
Thermistors
are
used to sense outdoor
ambient
(OAT) and coil temperature
(OCT).
Refer
to Fig. 25 for resistance
values versus
temperature.
See Fig.
26 for OCT location.
If the outdoor
ambient
or coil thermistor
should
fail,
the HP/AC
control
will flash the appropriate
fault code (See Table 5).
IMPORTANT:
Coil thermistor
is factory
mounted.
Check
to
insure
thermistor
is mounted
properly.
Outdoor
air thermistor
(OAT)
is field mounted
and connected.
Verify
that the OAT has
been properly
installed.
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF