Carrier Infinity 48XL Installation Instructions Manual page 34

15 seer single packaged air condotioner and gas furnace system with puron (r-410a) refrigerant
Hide thumbs Also See for Infinity 48XL:
Table of Contents

Advertisement

Table 9
- Troubleshooting
Chart
SYMPTOM
Compressor
and outdoor fan
will not start
Compressor
will not start but condenser
fan
runs
Compressor
cycles (other than normally sat-
isfying)
cooling/heating
calls
Compressor
operates continuously
Excessive
head
pressure
Head pressure too low
Excessive suction pressure
Suction pressure too low
IFM does not run
IFM operation
is intermittent
CAUSE
Power failure
Fuse blown or circuit breaker tripped
Defective contactor, transformer,
control relay, or high-
pressure, loss-of-charge
or low-pressure
switch
Insufficient line voltage
Incorrect or faulty wiring
UI setting too low/too high
Units
have
a 5-minute
time
delay
Faulty wiring or circuit
Loose connections
in compressor
Compressor
motor burned out, seized, or
internal overload open
Defective run capacitor, overload, or PTC (positive
temperature
coefficient) thermistor
Low input voltage (20 percent low)
Refrigerant
overcharge
or undercharge
Defective compressor
Insufficient line voltage
Blocked outdoor coil
Defective run/start capacitor, overload or start relay
Faulty outdoor fan motor or capacitor
Restriction in refrigerant system
Dirty air filter
Unit undersized for load
UI temperature
set too low
Low refrigerant
charge
Air in system
Outdoor coil dirty or restricted
Dirty air filter
Dirty indoor or outdoor coil
Refrigerant
overcharged
Air in system
Indoor or outdoor air restricted
or air short-cycling
Low refrigerant
charge
Restriction in liquid tube
High heat load
Reversing valve hung up or leaking internally
Refrigerant
overcharged
Dirty air filter
Low refrigerant
charge
Metering device or low side restricted
Insufficient coil airflow
Temperature
too low in conditioned
area
Outdoor ambient below 55°F (13°C)
Filter drier restricted
Blower wheel not secured to shaft
Insufficient voltage at motor
Power connectors
not properly sealed
Water dripping into motor
Connectors
not firmly sealed
REMEDY
Call power company
Replace fuse or reset circuit breaker
Replace component
Determine cause and correct
Check wiring diagram and rewire correctly
Reset UI setting
DO NOT bypass this compressor
time
delay-wait
for 5 minutes until time-delay
relay is de-energized
Check wiring and repair or replace
Determine cause
Replace compressor
Determine cause and replace
Determine cause and correct
Recover refrigerant, evacuate system, and re-
charge to capacities
shown on rating plate
Replace and determine
cause
Determine cause and correct
Determine cause and correct
Determine cause and replace
Replace
Locate restriction and remove
Replace filter
Decrease load or increase
unit size
Reset UI setting
Locate leak, repair, and recharge
Recover refrigerant, evacuate system, and re-
charge
Clean coil or remove restriction
Replace filter
Clean coil
Recover excess
refrigerant
Recover refrigerant, evacuate system, and re-
charge
Determine cause and correct
Check for leaks, repair and recharge
Remove restriction
Check for source and eliminate
Replace valve
Recover excess refrigerant
Replace filter
Check for leaks, repair and recharge
Remove source of restriction
Check filter-replace
if necessary
Reset UI setting
Verify low-ambient
cooling enabled in UI
Replace
Properly tighten blower wheel to shaft
Determine
cause and correct
Connectors
should snap easily; do not force
Verify proper drip loops in connector
wires
Gently pull wires individually to be sure they are
crimped into the housing
34