Carrier Infinity 48XL Installation Instructions Manual page 22

15 seer single packaged air condotioner and gas furnace system with puron (r-410a) refrigerant
Hide thumbs Also See for Infinity 48XL:
Table of Contents

Advertisement

INFINITY
CONTROLLED
LOW AMBIENT
COOLING
NOTE:
When this unit is operating
below
55°F
(13°C)
outdoor
temperature,
provisions
must
be made
for low ambient
operation.
This
unit
is capable
of
low
ambient
cooling
down
to
0°F
(-18°C).ONLY
when using the Infinity
control.
A low ambient
kit
is not required,
and the outdoor
fan motor
does not need
to be
replaced
for
Infinity
controlled
low
ambient
operation.
Low
ambient
cooling
must
be enabled
in the UI set-up.
Fan may not
begin
to cycle until about 40°F
(4°C).OAT.
Fan will cycle based
on coil
and
outdoor
air temperature.
Infinity
controlled
low
ambient
mode operates
as follows:
• In high stage, fan is off when
outdoor
coil temp is <outdoor
air
temperature
plus 3 ° F (1.7 ° C) or outdoor
fan has been ON for 30
minutes.
(Fan
is turned
off to allow
refrigerant
system
to
stabilize.)
• In low stage, fan is off when outdoor
coil temp is <outdoor
air
temperature
plus 1 °F (.6°C)
or outdoor
fan has been ON for 30
minutes.
(Fan
is turned
off to allow
refrigerant
system
to
stabilize.)
• In high stage and low stage, fan is on when
outdoor
coil temp >
outdoor
air temperature
plus 25 °F (13.8 ° C) or outdoor
coil temp
> 80°F
(27°C)
or if outdoor
fan has been OFF for 30 minutes.
(Fan is turned on to allow refrigerant
system to stabilize.)
• Low-pressure
switch
is ignored
for first 3 minutes
during
low
ambient
start up. After 3 minutes,
if LPS trips, then outdoor
fan
motor is turned off for 10 minutes with the compressor
running.
If
LPS closes within
10 minutes
then cooling
continues
with the
outdoor
fan cycling
per the coil temperature
routine
listed above
for the remainder
of the cooling
cycle. If the LPS does not close
within 10 minutes,
then the normal LPS trip response
(shut down
cooling
operation
and generate
LPS trip error) will occur.
DEHUMIDIFICATION
MODE
This Infinity
system
can be used to dehumidify
the living
space.
See UI Installation
Instructions
for more details.
SEQUENCE
OF OPERATION-GAS
HEAT
NOTE:
Infinity
control must be grounded
for proper
operation
or
control will lock out.
NOTE:
If a power
interruption
occurs
during
a call for heat, the
control will start a 90-second
blower
only ON period two seconds
after power
is restored,
if the UI is still calling
for gas heating.
The
amber
LED light will flash code 12 during
the 90-second
period,
after which
the LED will be ON continuously,
as long as no faults
are detected.
After the 90-second
period,
the unit will respond
to
the UI normally.
GAS HEAT MODE
AND ADJUSTMENTS
When the UI calls for gas heat, the Infinity
furnace board performs
a self-check,
verifies
the pressure
switch
is open,
and starts the
inducer
on high speed.
1. Inducer
Pre-purge
Period:
When the inducer
motor comes
up on
high
speed,
the
pressure
switch
closes,
and the
Infinity
ignition
control
on the furnace
board
begins
a 15
second
pre-purge
period.
If the pressure
switch
fails to
remain
closed,
the inducer
will remain
running.
After the
pressure
switch
re-closes,
the Infinity
ignition
control
will
begin
a 15 second
pre-purge
period.
2. Trial-For-Ignition
Sequence:
The spark igniter
will spark
for 3 seconds.
The main gas valve relay contact
closes to
energize
the gas valve
on low stage.
After 5 seconds,
the
igniter
is de-energized
and
a 2-second
flame-proving
period
begins.
NOTE:
The unit always
lights
on high
speed inducer
and low stage gas valve operation.
3. Flame-Proving:
When
the burner
flame
is proved
at the
flame-proving
sensor,
the furnace
control
determines
what
heating
stage to run based on feedback
from the UI.
If the
UI is asking
for low stage gas heat, the ignition
control will
change
the inducer
speed
to low speed
and keep
the gas
valve
energized
on low stage.
If the UI is asking
for high
stage gas heat, the ignition
control
will maintain
running
the
inducer
on high
speed
and energize
the gas valve's
high
stage relay to increase
gas flow.
If the burner
flame is not proved
within 2 seconds,
the control will
close the gas valve
and repeat the ignition
sequence
up to 3 more
Trials-For-Ignition
before
going
to Ignition-Lockout.
Lockout
will reset automatically
after 3 hours,
by momentarily
interrupting
230
VAC power,
or by interrupting
24 VAC power
at SEC1
or
SEC2 to the furnace board.
If flame is proved
when
there should
be no flame present,
control
will lock out of Gas-Heating
mode
and operate
the inducer
motor
until flame is no longer proved.
4. Blower-On
Delay:
If
the
burner
flame
is
proven,
approximately
37 seconds
after the gas valve is opened
the
Indoor Blower
is turned on to the appropriate
speed for the
gas heating
stage.
Simultaneously,
the humidifier
terminal
HUM
and electronic
air
cleaner
terminal
EAC-I
are
energized
throughout
the
heating
cycle.
NOTE:
EAC-2
terminal
is common
with
L2 and will have
ll5VAC-to-ground
when unit is powered.
5. Blower-Off
Delay:
When the call for gas heat is satisfied,
the gas valve
is de-energized,
stopping
the flow of gas to
the burners,
and de-energizing
the HUM
terminal.
The
inducer
motor
will remain
on for a 4-second
post-purge
period.
The indoor
blower
and air cleaner
terminal
EAC-I
will
remain
energized
for 90, 120,
150,
or 180
seconds
(depending
on selection
of blower-off
delay selected
in the
UI).
The factory-set
default
is 120-second
blower-OFF
delay.
CHECK
GAS INPUT
(NATURAL
GAS)
[]NIT
DAMAGE
HAZARD
Failure
to follow
this caution
may
result
in component
damage.
Do
not
redrill
an
orifice.
Improper
drilling
(burrs,
out-of-round
holes,
etc.) can cause
excessive
burner
noise
and misdirection
of burner
flame.
If orifice
hole
appears
damaged
or it is suspected
to have
been
redrilled,
check
orifice hole with a numbered
drill bit of correct
size.
FIRE HAZARD
Failure
to follow
this
warning
could
result
in personal
iniury, death and/or property
damage.
DO NOT
bottom
out gas valve
regulator
adjusting
screws.
This can result
in unregulated
manifold
pressure
and result
in excess overfire
and heat exchanger
failures.
22

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF