Carrier Infinity 48XL Installation Instructions Manual page 24

15 seer single packaged air condotioner and gas furnace system with puron (r-410a) refrigerant
Hide thumbs Also See for Infinity 48XL:
Table of Contents

Advertisement

a.129 sec.
to complete
one revolution
b. 3600/129
= 27.9
c. 27.9 x 2 = 55.8 ft3 of gas flow/hr.
d. 55.8 x 1050 = 58,590
Btuh input.
In this example,
the nonfinal
input
rate for low
stage
is 58,500
Btu/hr,
so the low stage manifold
pressure
is correctly
set.
If the measured
low stage
rate is too low, increase
the manifold
pressure
to increase
rate.
If the measured
low stage rate is too high,
decrease
the manifold
pressure
to decrease
rate.
NOTE:
Double-check
that UI is running
on low stage gas heat
while clocking
the low stage firing rate.
4. Verify proper
low stage gas heat temperature
rise.
a. Furnace
must operate
within
rise range listed on rating
plate.
b. Select "COMFORT"
or "EFFICIENCY"
mode
on UI.
"COMFORT"
mode will provide
a warmer
supply
air
temperature,
while
"EFFICIENCY"
will provide
lower
gas consumption.
c. Make sure access panel is re-installed
on the unit.
d. Measure
supply
and return temperatures
as close to the
unit as possible.
Subtract
the return temperature
from
the supply temperature
to deternfine
rise. Rise should
fall within
the range specified
on the rating plate.
5.
Adjust
manifold
pressure
to obtain
high
stage
input
rate
(See Fig. 19).
a. Set unit to run for 20 minutes
in high-stage
gas heat
operation
using the "INSTALLER
CHECKOUT"
menu
on the UI.
b. Remove
regulator
adjustment
cap from high stage gas
valve pressure
regulator
(See Fig. 19) and turn
high-stage
adjusting
screw (3/16 or smaller
flat-tipped
screwdriver)
counterclockwise
(out) to decrease
rate and
clockwise
(in) to increase
input rate.
NOTE:
DO NOT
set high stage manifold
pressure
less than 3.2
IN.W.C.
or more
than 3.8 IN. W.C. for natural
gas.
If manifold
pressure
is outside
this range, change
main burner orifices.
c. Re-install
high stage regulator
adjustment
cap.
d. Leave manometer
connected.
6. Verify natural
gas high stage input rate.
a. Turn off all other gas appliances
and pilots served by
the gas meter.
b. If unit is not running,
set unit to run for 20 minutes
in
high stage gas heat operation
using the "INSTALLER
CHECKOUT"
menu on the UI.
c. Record
number
of seconds
for gas meter to complete
1
revolution.
d. Divide number
of seconds
in step c. into 3600 (number
of seconds
in 1 hour).
e. Multiply
result of step d. by the number
of cubic feet
shown
for one revolution
of test dial to obtain
cubic feet
of gas flow per hour.
f. Multiply
result of step f. by Btu heating
value of the gas
to obtain
total measured
input shown
in Table 4.
(Consult
the local gas supplier
if the heating
value of
gas is not known).
EXAMPLE:
Assume
a 90,000
high
stage
input
unit is being
installed.
Assume
that
the size of the dial is 2 cubic
ft., one
revolution
takes 84 sec., and the heating
value
of the gas is 1050
Btu/ft3.
Proceed
as follows:
a. 84 sec. to complete
one revolution
b. 3600/84
= 42.9
c. 42.9 x 2 = 85.8 ft3 of gas flow/hr.
d. 85.8 x 1050 = 90,090
Btuh input.
In this example, the nonfinal input rate for high stage is 90,000
Btu/hr, so the high stage manifold pressure is correctly set.
If the measured high stage rate is too low, increase the manifold
pressure to increase rate. If the measured high stage rate is too
high, decrease the manifold pressure to decrease rate.
NOTE:
Double-check that User Interface is running on high stage
gas heat while clocking the low stage firing rate.
7. Verify proper high stage gas heat temperature rise.
a. Furnace must operate within rise range listed on rating
plate.
b. Make sure access panel is re-installed on the unit.
c. Measure supply and return temperatures as close to the
unit as possible.
Subtract the return temperature from
the supply temperature to deternfine rise. Rise should
fall within the range specified on the rating plate.
NOTE:
If the temperature rise is outside the rating plate range,
first check:
a. Gas input for low and high stage gas heat operation.
b. Derate for altitude, if applicable.
c. Return and supply ducts for excessive restrictions
causing static pressures in excess of .5 IN. W.C.
d. Make sure model plug is installed.
8. Final Check
a. Turn off gas to unit
b. Remove manometer from pressure tap.
c. Replace pipe plug on manifold (See Fig. 20).
d. Turn on gas to unit.
e. Check for leaks.
CHECK GAS INPUT (PROPANE GAS)
Refer to propane kit installation instructions for properly checking
gas input.
NOTE:
For installations below 2,000 ft (610 m), refer to the unit
rating plate for proper propane conversion kit.
For installations
above 2,000 ft (610 m), contact your distributor for proper propane
conversion kit.
CHECK
BURNER
FLAME
With
burner
access
panel
removed,
observe
the
unit
heating
operation.
Watch the burner
flames to see if they are light blue and
soft in appearance,
and that the flames are approximately
the same
for each burner.
Propane
will have blue flame (See Fig. 21). Refer
to the Maintenance
section for information
on burner
removal.
MANIFOLD
PIPE PLUG
Fig. 20 - Burner
Assembly
099019
24

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save Article as PDF