Sequence Of Operation - Carrier Infinity 48XL Installation Instructions Manual

15 seer single packaged air condotioner and gas furnace system with puron (r-410a) refrigerant
Hide thumbs Also See for Infinity 48XL:
Table of Contents

Advertisement

If
thermistor is shorted
or open,
replace
it to return
the system
to
normal
operation.
If fault is in the wiring
connections,
correcting
the fault
will
clear
the
code
and return
the
system
to normal
operation.
NOTE:
If fault condition
is an open thermistor
or a wiring
problem
that appears
to be an open
thermistor
and the power
to the unit is
cycled off, the fault code will be cleared on the next power-up
but
the fault will remain
and system
operation
will not be as expected.
This
is because
on power-up,
the unit control
cannot
discern
the difference
between
an open
sensor
or if a sensor
is not
installed.
Sequence
of Operation
The
48XL
packaged
unit
is designed
for
installation
with
a
communicating
UI.
This
unit
will
not
respond
to
commands
provided
by a common
thermostat
except under certain
emergency
situations
described
in Step l--Start-Up
and Troubleshooting.
The UI uses temperature,
humidity
and other data supplied
from
indoor
and
outdoor
system
components
to control
heating
or
cooling
system
for optimum
comfort.
The unit will be commanded
by UI to supply
airflow. The unit will operate
the indoor
blower
at
requested
airflow
for most modes.
INDOOR
AIRFLOW
ADJUSTMENTS
The nominal
requested
airflow
for air conditioner
operations
will
be 350 cfm per ton of nominal
cooling
capacity
as defined
by unit
size. Actual
airflow
request
will be adjusted
from
nominal
using
indoor
and
outdoor
temperature
and
indoor
humidity
data
to
optimize
the system
operation
for occupant
comfort
and system
efficiency.
Refer to UI literature
for further
system control
details.
UNIT
OPERATION
HAZARD
Failure to follow
this caution
may result in unit damage.
For cooling
operation,
the recommended
airflow
is 350 to
450 cfm for each 12,000
Btuh of rated cooling
capacity.
For
heating
operation,
the airflow
must produce
a temperature
rise that falls within
the range
stamped
on the unit rating
plate.
For gas heat operations,
Table 3 shows
the temperature
rise in each
gas heating
mode.
Refer
to these
tables
to determine
the desired
heating
airflow for the system
being installed.
NOTE:
Be sure that all supply-and
return-air
grilles
are open,
free from
obstructions,
and
adjusted
properly.
Airflow
can be
changed
using
the UI. See UI installation
instructions
for more
detail.
NOTE:
Once the compressor
has started and then has stopped,
it
should
not be started
again
until
4 minutes
have
elapsed.
The
cooling
cycle
remains
:'on"
until the room
temperature
drops
to
point that is slightly
below
the cooling
control
setting of the UI.
AIR CONDITIONER
SEQUENCE
OF OPERATION
COOLING
OPERATION
With a call for first stage
cooling,
the outdoor
fan, and low stage
compressor
are
energized.
If low-stage
cannot
satisfy
cooling
demand,
high-stage
cooling
is energized
by the UI. After second
stage is satisfied,
the unit returns
to low-stage
operation
until first
stage is satisfied
or until second
stage is required
again. When both
first stage
and second
stage cooling
are satisfied,
the compressor
will shut off.
NOTE:
When
two-stage
unit is operating
at low-stage,
system
vapor (suction)
pressure
will be higher
than a standard
single-stage
system
or high-stage
operation.
NOTE:
Outdoor
fan motor
will continue
to operate
for one
minute
after compressor
shuts off, when outdoor
ambient
is greater
than or equal to 100°F (38°C).
UTILITY
INTERFACE
WITH
INFINITY
CONTROL
The
utility
curtailment
relay
should
be
connected
to
factory
supplied
pigtails
(PINK,
connected
to R, VIOLET
connected
to Y2
on the control
board)
located
in the low voltage
splice
box (See
Fig.
13, 14 and 16). This
input
allows
a power
utility device
to
interrupt
compressor
operation
during peak load periods.
When the
utility sends
a signal to shut the system
down,
the UI will display
"Curtailment
Active".
COMPRESSOR
OPERATION
When
the compressor
is operating
in low stage,
the modulating
ring is deactivated,
allowing
two internal
bypass
ports to close off
33% of the scroll compression
area so the system
operates
at part
load
capacity.
The
24-volt
solenoid
coil
is de-energized
in
low-stage
operation.
When
the compressor
is operating
at high
stage,
the modulating
ring
is activated,
sealing
the
bypass
ports,
which
allows
the
compressor
to operate
at full load capacity.
The 24-volt
solenoid
coil is energized
in high stage operation.
CRANKCASE
HEATER
OPERATION
(IF APPLICABLE)
The crankcase
heater
is energized
during
off cycle below
65°F
(18 ° C) outdoor
air temperature.
OUTDOOR
FAN MOTOR
OPERATION
The outdoor
unit control
energizes
the outdoor
fan any time the
compressor
is operating.
The outdoor
fan remains
energized
if a
pressure
switch
or compressor
overload
should
open. Outdoor
fan
motor will continue
to operate
for one minute
after the compressor
shuts
off when
the outdoor
ambient
is greater
than or equal
to
100°F
(38°C).
TIME
DELAYS-AIR
CONDITIONER
OPERATIONS
The unit time delays include:
• Five minute time delay to start cooling
operation
when there is a
call from the thermostat
or user interface.
To bypass
this feature,
momentarily
short and release Forced
Defrost
pins.
• Five minute compressor
recycle
delay on return from a
brown-out
condition.
• Two minute time delay to return to standby
operation
from last
valid communication
(with Infinity
only).
• One minute
time delay of outdoor
fan at termination
of cooling
mode when outdoor
ambient
is greater
than or equal to 100°F
(38°C).
• There is no time delay between
air conditioner
staging
from low
to high and from high to low capacity;
the compressor
will change
from
low to high
and from
high
to low capacity
as demand
dictates.
20

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF