Carrier Infinity 48XL Installation Instructions Manual page 23

15 seer single packaged air condotioner and gas furnace system with puron (r-410a) refrigerant
Hide thumbs Also See for Infinity 48XL:
Table of Contents

Advertisement

CARBON MONOXIDE POISONING
HAZARD
Failure
t o follow
this warning
could
result
in personal
iniury and/or death.
If the manifold
pressure
and/or
gas rate
is not properly
adjusted
on HI and LO stages, excess carbon
monoxide
can
be produced.
FIRE
AND UNIT DAMAGE
HAZARD
Failure
to follow
this warning
could
result
in personal
iniury or death and/or property
damage.
Unsafe
operation
of the unit may result if manifold
pressure
is outside
of the ranges listed in Table 6.
Gas input rates on rating plate are for installations
at altitudes
up to
2000 ft (610 m).
Input rate must be within
- 2% of rating
plate
input.
1. Determine
the correct gas input rate.
a. The rated gas inputs shown
in Table 4 are for altitudes
from sea level to 2000 ft (610 m) above sea level.
These inputs
are based on natural gas with a heating
value of 1050 Btu/ft3
at .65 specific gravity.
IN THE U.S.A.:
The input
rating
for altitudes
above
2,000
ft
(610
m) must
be
reduced
by 4 percent
for each 1,000 ft (305 m) above sea level.
For installations
below
2,000
ft, (610
m) refer to the unit rating
plate.
For installations
above 2,000 ft, (610 m) multiply
the input by on
the rating plate
by the derate
multiplier
in Table 6 for the correct
input rate.
Table
5 - Altitude
Derate
Multiplier
for U.S.A.
Derate
Multiplier
Altitude
ft (m)
Percent
of Derate
Factor*
0-2000
(0-610)
0
1.00
2001-3000
(610-914)
8-12
0.90
3001-4000
(915-1219)
12-16
0.86
4001-5000
(1220-1524)
16-20
0.82
5001-6000
(1524-1829)
20-24
0.78
6001-7000
(1829-2134)
24-28
0.74
7001-8000
(2134-2436)
28-32
0.70
8001-9000
(2139-2743)
32-36
0.66
9001-10,000
36-40
0.62
(2744-3048)
:'Derate multiplier factors are based on midpoint altitude for altitude range,
IN CANADA:
The input rating for altitudes
from 2,000 (610 m) to 4,500 ft (1372
m) above
sea level must
be derated
10 percent
by an authorized
Gas Conversion
Station or Dealer.
EXAMPLE:
90,000
Btuh Input Furnace
Installed
at 4300 ft (1372 m).
Furnace Input Rate
Derate Multiplier
Furnace Input Rate
at Sea Level
X
Factor
at Installation
Altitude
90,000
X
0.90
=
81,000
b. When the gas supply being used has a different
heating
value or specific gravity,
refer to national
and local
codes, or contact
your distributor
to determine
the
required
orifice
size.
2. Adjust
manifold
pressure
to obtain
low stage input rate (See
Fig. 19).
a. Turn off gas supply to unit.
b. Remove
pipe plug on manifold
(See Fig. 20) and
connect
manometer.
Turn on gas supply
to unit.
c. Turn gas valve switch to ON.
d. Set unit to run for 20 minutes
in low-stage
gas heat
operation
using the "INSTALLER
CHECKOUT"
menu
on the User Interface.
e. Remove
regulator
adjustment
cap from low stage gas
valve pressure
regulator
(See Fig. 19) and turn
low-stage
adjusting
screw (3/16 or smaller
flat-tipped
screwdriver)
counterclockwise
(out) to decrease
rate and
clockwise
(in) to increase
input rate.
1/2"
NPT iNLET
1/2'
NPT
OUTLET
J
_
PD AE_'/FOLDE
TAP
Fig. 19 - Redundant
Automatic
Gas Control
Valve
A04167
NOTE:
DO NOT set low stage manifold
pressure
less than 1.4
IN. W.C.
or more than 2.0 IN. W.C. for natural
gas.
If manifold
pressure
is outside
this range, change main burner
orifices.
f. Re-install
low stage regulator
adjustment
cap.
g. Leave manometer
connected.
NOTE:
If orifice hole appears
damaged
or it is suspected
to have
been re-drilled,
check orifice
hole with a numbered
drill bit of the
correct
size.
Never
re-drill
an orifice.
A burr-free
and squarely
aligned
orifice hole is essential
for proper
flame characteristics.
3. Verify natural
gas low stage input rate.
a. Turn off all other gas appliances
and pilots
served by
the gas meter.
b. If unit is not running,
set unit to run for 20 minutes
in
low-stage
gas heat operation
using the "INSTALLER
CHECKOUT"
menu on the UI.
c. Record
number
of seconds
for gas meter to complete
one revolution.
d. Divide
number
of seconds
in step c. into 3600 (number
of seconds
in 1 hour).
e. Multiply
result of step d. by the number
of cubic feet
shown
for one revolution
of test dial to obtain
cubic feet
of gas flow per hour.
f. Multiply
result of step f. by Btu heating
value of the gas
to obtain
total measured
input shown
in Table 4.
(Consult
the local gas supplier
if the heating
value of
gas is not known).
EXAMPLE:
Assume
a 90,000
high
stage
input
unit is being
installed.
Assume
that the
size of the
dial is 2 cubic
ft., one
revolution
takes 129 sec., and the heating
value of the gas is 1050
Btu/ft3.
Proceed
as follows:
23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF