Commissioning
6.4

Calling the Commissioning Quick Setup

All the functions needed for commissioning are called up automatically with the Quick Setup.
The functions can be changed and adapted to suit the individual processes.
F Enter the function matrix (starting with measured value display)
1.
P Select the group QUICK SETUP
2.
F Confirm selection
3.
QUICK SETUP COMMISSIONING function appears.
4.
Intermediate step if configuration is blocked:
P Enter the code 93 (confirm with F ) and thus enable configuration
P Go to Commissioning Quick Setup
5.
P Select YES
6.
F Confirm selection
F Start Commissioning Quick Setup
7.
8.
Configure the individual functions/settings:
– Via P-key, select option or enter number
– Via F-key, confirm entry and go to next function
– Via Q-key, return to Setup Commissioning function
(settings already made are retained)
!
. Note!
Observe the following when performing the Quick Setup:
• Configuration selection: Select the ACTUAL SETTING option
• Unit selection: This is not offered again for selection after configuring a unit
• Output selection: This is not offered again for selection after configuring an output
• Automatic configuration of the display: select YES
– Main line = volume flow
– Additional line = totalizer 1
– Information line = operating/system condition
• If asked whether additional Quick Setups should be executed: select NO
All the available functions of the measuring device and their configuration options as well as
additional Quick Setups, if available, are described in detail in the "Description of Device
Functions" Operating Instructions. The related Operating Instructions can be found on the
CD-ROM.
The measuring device is ready for operation on completion of the Quick Setup.
6.5

Troubleshooting

A complete description of all the error messages is provided in the Operating Instructions on the
CD-ROM.
!
. Note!
The output signals (e.g. pulse, frequency) of the measuring device must correspond to the
higher-order controller.