GENERAL

The EconoMi$er
X system utilizes the latest technology
®
available for integrating the use of free cooling with mechanical
cooling for packaged rooftop units. The code compliant W7220
control system optimizes energy consumption, zone comfort, and
equipment cycling by operating the compressors when the out-
door-air temperature is too warm, integrating the compressor with
outdoor air when free cooling is available, and locking out the
compressor when outdoor-air temperature is too cold. Demand
control ventilation is supported.
This EconoMi$er X system can be used with 1 or 2 speed indoor
fan motor units. (All other speed settings listed are for future use.)
The EconoMi$er X system utilizes gear-drive technology with a
direct-mount spring return actuator that will close upon loss of
power. The EconoMi$er X system comes standard with fault
detection and diagnostics (FDD), an outdoor air temperature
sensor, and mixed air temperature sensor (also called supply air
temperature sensor). Outdoor enthalpy, indoor (return) dry bulb or
enthalpy, and CO
sensors are available for field installation.
2
Standard integrated barometric relief dampers provide natural
building pressurization control. An optional power exhaust system
is available for applications requiring even greater exhaust
capabilities. The power exhaust set point is adjustable at the
EconoMi$er X controller.
See Tables 1-3 for package usage. See Table 4 for package
contents. See Table 5 for sensor usage.
IMPORTANT: These economizers meet all the economizer
requirements as specified in ASHRAE 90.1, IECC and
California's Title 24. Economizer must be installed square to
avoid damper leakage or damper binding. Squareness tolerance
is ± 1/32-in.
IMPORTANT: Read these instructions completely before
attempting to install the accessory economizer.
Table 1 — Carrier Usage Chart
CARRIER MODEL NUMBER
Small Cabinet
48/50FC*04-07
48/50GC*04-06
48/50HC 04-06
4850LC 04-06
48/50KC 04-06
48/50TC 04-07
50FCQ 04-07
50GCQ 04-06
50HCQ 04-06
50KCQ 04-06
50TCQ 04-07
Large Cabinet
48/50HC 07-12
48/50LC 07
48/50TC 08-14
50HCQ 07-09
50TCQ 08-12
Extra Large Cabinet
48/50HC 14
48/50LC 08-12
48/50TC 16
50HCQ 12
50TCQ 14
ECONOMI$ER
X PART NUMBER
®
CRECOMZR067A01
CRECOMZR069A01
CRECOMZR071A01
Table 2 — Bryant Usage Chart
BRYANT MODEL NUMBER
582K/559K 04-07
581K/551K 04-06
581J/551J 04-06
582J559J 04-06
580J/558J 04-07
547K 04-07
549K 04-06
549J 04-06
547J 04-06
548J 04-07
581J/551J 07-12
580J/558J 08-14
549J 07-09
548J 08-12
Extra Large Cabinet
581J/551J 14
580J/558J 16
549J 12
548J 14
Table 3 — ICP Usage Chart
ICP MODEL NUMBER
RGV/RAV 036-072
RGW/RAW 036-060
RGH/RAH 036-060
RGX/RAX 036-060
RGS/RAS 036-072
RHX/RHH 036-060
RHV 036-072
RHW 036-060
RHS 036-072
RGH/RAH 072-120
RGS/RAS 090-150
RHH 072-102
RHS 090-120
Extra Large Cabinet
RGH/RAH 150
RGS/RAS 150
RHH 120
RHS 150
2
ECONOMI$ER
X PART NUMBER
®
Small Cabinet
CRECOMZR067A01
Large Cabinet
CRECOMZR069A01
CRECOMZR071A01
ECONOMI$ER
X PART NUMBER
®
Small Cabinet
CRECOMZR067A01
Large Cabinet
CRECOMZR069A01
CRECOMZR071A01