Checkout Tests - Bryant 582K Installation Instructions Manual

3 to 12.5 tons (48/50lc 14 not included) accessory ultra low leak vertical economiser x
Hide thumbs Also See for 582K:
Table of Contents

Advertisement

MENU
PARAMETER
DAMPER VMIN-HS
DAMPER VMAX-HS
DAMPER OPEN
DAMPER CLOSE
CONNECT Y1-O
CHECKOUT
CONNECT Y2-O
CONNECT AUX1O
Alarms display only when they are active. The menu title "ALARMS(_)" includes the number of active alarms in parenthesis ( ).
MA T SENS ERR
CO2 SENS ERR
OA T SENS ERR
OA SYLK SENS
ERR
DA T SENS ERR
ALARMS(_)
SYS ALARM
ACT UNDER V
ACT OVER V
ACT STALLED
LEGEND
LCD — Liquid Crystal Display
MAT — Mixed Air Temperature
OAT — Outdoor Air Temperature
OCC — Occupied
RAT — Return Air Temperature
RTU — Rooftop Unit

Checkout Tests

Use the Checkout menu (see Table 11) to test the damper
operation and any configured outputs. Only items that are
configured are shown in the Checkout menu.
NOTE: See User Interface for information about menu navigation
and use of the keypad.
1.
To perform a Checkout test:
2.
Scroll to the desired test in the Checkout menu using the ▲
and ▼ buttons.
3.
Press the
button to select the item.
4.
RUN? appears.
5.
Press the
button to start the test.
6.
The unit pauses and then displays IN PROGRESS.
7.
When the test is complete, DONE appears.
8.
When all desired parameters have been tested, press the
(Menu up) button to end the test.
Checkout test can be performed at any time during the operation
of the system as a test that the system is operable.
Table 11 — Menu Structure* (cont)
PARAMETER
PARAMETER
DEFAULT
RANGE AND
VALUE
INCREMENT†
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Positions OA damper to VMIN High Speed position
Positions OA damper to VMAX High Speed position
Positions OA damper to the full open position.
Positions damper to the fully closed position
Closes the Y1—O relay (Y1—O)
Closes the Y2—O relay (Y2—O)
Energizes the AUX1O output. If Aux setting is:
• NONE= not action taken
• ERV = 24 Vac out. Turns on or signals an ERV that the conditions are not
good for economizing but are for ERV operation††
• SYS = 24 Vac out. Issues a system alarm
MIXED AIR TEMPERATURE SENSOR ERROR
CO2 SENSOR ERROR
OUTSIDE AIR TEMPERATURE SENSOR ERROR
OAT sensor connected at input terminals OAT
OUTSIDE AIR ENTHALPY SENSOR ERROR
OAT sensor connected on S—bus
DISCHARGE AIR TEMPERATURE SENSOR ERROR
When AUX1-0 is set to SYS and there is any alarm (e.g., failed sensors,
etc.), the AUX1-0 terminal has 24 Vac out.
ACTUATOR VOLTAGE LOW
Voltage received at actuator is below expected range
ACTUATOR VOLTAGE HIGH
Voltage received at actuator is above expected range
ACTUATOR STALLED
Actuator stopped before reaching commanded position.
*
Table 11 illustrates the complete hierarchy. The menu parameters
may be different depending on the configuration. For example, if
there is no DCV (CO
) sensor, then none of the DCV parameters
2
appear.
† When values are displayed, pressing and holding the ▲ or ▼ button
causes the display to automatically increment.
** N/A = Not Applicable.
†† ERV Operation: When in cooling mode AND the conditions are NOT
OK for economizing - the ERV terminal will be energized. In the
Heating mode, the ERV terminal will be energized when the OA is
below the ERV OAT setpoint in the setpoint menu.
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
Be sure to allow enough time for compressor start-up and
shutdown between checkout tests so that you do not short-
cycle the compressors.
21