Variable Frequency Drive (VFD)
F ac t ory -I n stal l e d O pt i o n
2 - S p e e d M o t o r C o n t r o l
f o r 2 - S t a g e C o o l i n g R o o f t o p U n i t s
Installation, Start-Up and Service Instructions
This document provides supplemental installation, setup and troubleshooting information for the Vari-
able Frequency Drive (VFD) factory-installed option. It is to be used with the base unit Installation
Instructions for 548J/549J, 551J/558J, 580J/581J and 524J 2-Stage cooling units with a VFD fan speed
relay board, sizes 07-30. Units equipped with the VFD are identified by an indicator in the unit's model
number (see the unit's nameplate). Use Table 1 to identify whether a given unit is equipped with the
factory-installed VFD option.
NOTE: Read the entire instruction manual before starting the
installation.
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Identifying Factory Option . . . . . . . . . . . . . . . . . . . . . . . . . 2
FAN MOTOR OPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Compressor Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Indoor Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Cooling with 2-Speed Indoor Fan Motor . . . . . . . . . . . . . 16
Cooling (FAN Switch in AUTO) . . . . . . . . . . . . . . . . . . . . 16
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Operating Fan for Test and Balance . . . . . . . . . . . . . . . . . 17
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Fan Speed Relay Board . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Configuration Jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Variable Frequency Drive . . . . . . . . . . . . . . . . . . . . . . . . . 18
VFD Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Control and Power Wiring Diagrams . . . . . . . . . . . . . . . . 22
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 29
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
VFD MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Heat Sink Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Fan Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Bypass the VFD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
VFD PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
VFD REMOTE KEYPAD . . . . . . . . . . . . . . . . . . . . . . . . . 45
ACH550/ACS320 VFD Modes . . . . . . . . . . . . . . . . . . . . . . 45
ACH550/ACS320 VFD Diagnostics . . . . . . . . . . . . . . . . . . 47
Correcting Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53580024-01
Page
Printed in U.S.A.
Form No. IIVFD-12
Reset After Using Start-Up Assistant . . . . . . . . . . . . . . . . 50
ACH580 Operation with Remote Keypad . . . . . . . . . . . . 51
ACH580 VFD Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
ACH580 VFD Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . 54
Control Panel Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
VFD Remote Keypad Parameters . . . . . . . . . . . . . . . . . . 57

SAFETY CONSIDERATIONS

CAUTION
CONFIGURATION OVERRIDE HAZARD
Do not use start-up assistant on this VFD application. Use
of start-up assistant will override the factory VFD
configurations.
Improper installation, adjustment, alteration, service, mainte-
nance, or use can cause explosion, fire, electrical shock or other
conditions which may cause personal injury or property damage.
Consult a qualified installer, service agency, or your distributor or
branch for information or assistance. The qualified installer or
agency must use factory-authorized kits or accessories when mod-
ifying this product. Refer to the individual instructions packaged
with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloths for brazing operations and have a fire extin-
guisher available. Read these instructions thoroughly and follow
all warnings or cautions attached to the unit. Consult local build-
ing codes and appropriate national electrical codes (in USA,
ANSI/NFPA70, National Electrical Code (NEC); in Canada,
CSA C22.1) for special requirements.
It is important to recognize safety information. This is the safety-
alert symbol
. When you see this symbol on the unit and in in-
structions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices, which may result in minor personal
injury or product and property damage.
NOTE is used to highlight suggestions which will result in
enhanced installation, reliability, or operation.
Pg 1
1-24
Replaces: IIVFD-11

Advertisement

Table of Contents
loading

Summary of Contents for Bryant 580J

  • Page 1: Table Of Contents

    Frequency Drive (VFD) factory-installed option. It is to be used with the base unit Installation Instructions for 548J/549J, 551J/558J, 580J/581J and 524J 2-Stage cooling units with a VFD fan speed relay board, sizes 07-30. Units equipped with the VFD are identified by an indicator in the unit's model number (see the unit's nameplate).
  • Page 2: General

    Nomenclature. 524J*07-25H Unit Installation with 2-Speed Indoor Fan Motor Option 581J/551J, 548J/549J AND 580J/558J ROOFTOP Refer to the base unit installation instructions for standard required operating and service clearances. 1. Third-party trademarks and logos are the property of their respective...
  • Page 3 Outdoor Air Options Cooling Tons Indoor Fan Options Refrig. System/Gas Heat Options Coil Options Heat Level (Btuh) Fig. 4 — Model Number Nomenclature Example, 580J/558J/548J/581J/551J/549J Series Position: 9 10 11 12 13 14 15 16 17 Example: Product Type Packaging...
  • Page 4 581J*11 3000 3380 2231 581J*12 3000 3380 2231 581J*14 3750 4225 2789 Table 2 — 580J Min cfm Per Fan Motor Type 581J*17 4500 5070 3346 2-SPEED FAN 2-SPEED FAN 581J*20 5250 5915 3904 SINGLE SPEED MODEL-SIZE...
  • Page 5: Pre-Start Check, 2-Speed Indoor Fan Motor Option

    Inspect wiring at the VFD for loose or disconnected wires at the terminal strip and for wires in contact with sharp edges and moving parts (pulley, belt). Variable Frequency Drive (VFD) Fig. 6 — ACS320 VFD Location for the following units: 580J/558J/548J*07 (208/230V and 460V units only)
  • Page 6 Variable Frequency Drive (VFD) Fig. 7 — ACH550/580 VFD Location for the following units: 580J/558J*07 (575V units only) Variable Frequency Drive (VFD) Fig. 8 — ACS320 VFD Location for the following units: 580J/558J*08 (208/230V and 460V units only)
  • Page 7 Variable Frequency Drive (VFD) Fig. 9 — ACH550/580 VFD Location for the following units: 580J/558J*08 (575V units only) Variable Frequency Drive (VFD) Fig. 10 — ACH550/580 VFD Location for the following units: 581J/551J*07 and 549J*07...
  • Page 8 Drive (VFD) Fig. 11 — ACS320 VFD Location for the following units: 580J/558J*09-14 and 548J*08-12 (208/230V and 460V units only) Variable Frequency Drive (VFD) Fig. 12 — ACH550/580 VFD Location for the following units: 580J/558J*09-14 and 548J*08-12 (575V units only)
  • Page 9 Variable Frequency Drive (VFD) Fig. 13 — ACH550/580 VFD Location for the following units: 581J/551J*08-09 and 549J*08-09 Variable Frequency Drive (VFD) Fig. 14 — ACS320 VFD Location for the following units: 580J/558J*16 and 548J*14 (208/230V and 460V units only)
  • Page 10 Drive (VFD) Fig. 15 — ACH550/580 VFD Location for the following units: 580J/558J*16 and 548J*14 (575V units only) Variable Frequency Drive (VFD) Fig. 16 — ACS320 VFD Location for the following units: 580J/558J*17-30, 548J*17-24 and 581J/551J*17-28 (208/230V and 460V units only)
  • Page 11 Variable Frequency Drive (VFD) Fig. 17 — ACH550/580 VFD Location for the following units: 580J/558J*17-30, 548J*17-24 and 581J/551J*17-28 (575V units only) Variable Frequency Drive (VFD) Fig. 18 — ACS320 VFD Location for the following units: 524J*07-12A, 524J*07-12H (208/230V and 460V only)
  • Page 12 Variable Frequency Drive (VFD) Fig. 19 — ACS320 VFD Location for the following units: 524J*14-25A, 524J*16-25H (208/230V and 460V only) Variable Frequency Drive (VFD) Fig. 20 — ACS320 VFD Location for the following units: 524J*28-30A (208/230V and 460V only)
  • Page 13 Variable Frequency Drive (VFD) Fig. 21 — ACH550/580 VFD Location for the following units: 524J*07-12A, 524J*07-12H (575V only)
  • Page 14 Variable Frequency Drive (VFD) Fig. 22 — ACH550/580 VFD Location for the following units: 524J*14-25A, 524J*16-25H (575V only)
  • Page 15 Variable Frequency Drive (VFD) Fig. 23 — ACH550/580 VFD Location for the following units: 524J*28-30A (575V only)
  • Page 16: Start-Up, 2-Speed Indoor

    (Continuous) position. Fan motor will start, run at reduced speed. The thermostat’s G terminal is energized with 24-v. This signal is conveyed to the 551J,580J/558J Series unit’s Central Terminal Check for fan rotation direction. To reverse the fan rotation, dis-...
  • Page 17: Heating

    29.3 r/s) range for High Speed. Indoor fan motor ramps down to stop. Replace the fan access panel. 580J/581J SERIES 10. Perform Test and Balance procedure. 11. Adjust the supply fan speed according to base unit instruc- The IGC’s fan-off delay sequence will energize relay K3 for tions to deliver the project selection cfm value.
  • Page 18: Service

    SERVICE Table 10 — Two-Speed Configuration Logic (Thermostat Control) CAUTION RELAY COIL STATUS CONTROLLING FAN MOTOR INPUT OUTPUT SPEED EQUIPMENT DAMAGE HAZARD Low (40 Hz) Failure to follow this caution will result in equipment Low (40 Hz) damage. High (60 Hz) DO NOT exceed the recommended minimum Hz or cfm High (60 Hz) settings.
  • Page 19 The 2-Speed Indoor Fan control circuit inputs to the VFD are The VFD used in the 2-Speed Indoor Fan Motor system has 24-VDC signals. soft start capabilities to slowly ramp up the speeds, eliminating any high inrush of air volume during speed changes. It also has •...
  • Page 20: Central Terminal Board Jumpers (548J/549J/551J/558J/580J/581J Series Only)

    ACH550/580ACH VFD TERMINAL STRIP Fig. 30 — ACH550/580 VFD Wiring Central Terminal Board Jumpers (548J/549J/551J/558J/580J/581J Series Only) The Central Terminal Board (CTB) is a large printed circuit board that is located in the unit control box. This printed circuit board contains multiple termination strips and connectors to simplify factory control box wiring and field control connections.
  • Page 21: Vfd Fuses

    VFD installed in 524J units. Check the control wiring diagram label on the specific unit in use for the fuse location. Table 15 — VFD Fuse Requirements, 558J/580J, 548J, 551J/581J, and 549J Units HARNESS UNIT VOLTAGE...
  • Page 22: Control And Power Wiring Diagrams

    Table 16 — VFD Fuse Requirements, 524J Units HARNESS UNIT VOLTAGE (ACS320/ACH550/ MOTOR STANDARDIZED FUSE FUSE P/N WIRE ACH580) GAUGE 208/230 HK30WA523 HD56FR233 30A - CLASS CC KTK HY10KB300 HK30WA530 HD56FR463 15A - CLASS CC KTK HY10KB151 HK30WA360 (550) HD56FR579 10A - CLASS CC KTK HY10KB101 HK30WB340 (580)
  • Page 23 Fig. 32 — Typical Wiring Diagram - Single Package Rooftop Unit (580J*07 with ACS320 VFD shown)
  • Page 24 Fig. 33 — Typical Wiring Diagram - Single Package Rooftop Unit (558J*07 with ACS320 VFD shown)
  • Page 25 Fig. 34 — Typical Wiring Diagram - Single Package Rooftop Unit (581J*14 with ACH550/ACH580 VFD shown)
  • Page 26 Fig. 35 — Typical Wiring Diagram - Single Package Rooftop Unit (551J*14 with ACH550/ACH580 VFD shown)
  • Page 27 Fig. 36 — Typical Wiring Diagram - Single Package Rooftop Unit (580J*17-30 and 581J*17-28 with ACS320 VFD shown)
  • Page 28 Fig. 37 — Typical Wiring Diagram - Single Package Rooftop Unit (558J*17-30 and 551J*17-28 with ACS320 VFD shown)
  • Page 29: Vfd Alarms And Faults Troubleshooting

    Fig. 38 — Typical Wiring Diagram - Split System Air-Handling Unit (524J with ACH550/ACH580 VFD shown) VFD ALARMS AND FAULTS CLEAR THE ALARM LED TROUBLESHOOTING Shut off power to the VFD for five minutes. Restore power and recheck the GREEN LED. If this LED is still flashing, The VFD has two LEDs ACH550/ACS320 or only one LED connect the accessory remote display keypad kit and follow ACH580 on its front panel that indicate VFD operating status.
  • Page 30: Vfd Maintenance

    VFD MAINTENANCE If installed in an appropriate environment, the VFD requires very little maintenance. Table 17 lists the routine maintenance intervals recommended by Bryant. Table 17 — Maintenance Intervals MAINTENANCE INTERVAL Every 6 to 12 months Heat sink temperature check...
  • Page 31: Fan Replacement

    Remove the remote keypad, if installed. See Fig. 45. process, fan replacement is recommended once these symptoms Remove the front cover by loosening the retaining screw. See start appearing. Replacement fans are available from Bryant. Fig. 46. ACH580 MAIN FAN REPLACEMENT Unplug fan power supply wires from the drive (see Fig.
  • Page 32 Fig. 48 — ACH550 Fan Replacement Fig. 46 — Remove Drive Cover ACS320 FAN REPLACEMENT (R1 and R2 Frame Sizes) To replace the fan perform the following: Remove power from drive. Wait for 5 minutes and then make sure by measuring that there is no voltage Insert a small straight blade screwdriver into the slot and press in to release the top cover as shown in See Fig.
  • Page 33: Bypass The Vfd

    If there is an occasion where the VFD has mis-functioned and temporary cooling/operation is required, bypass the VFD as shown in Fig. 51 and 52. To bypass ACS320 VFD on fused units – 580J/558J*07-14, 548J 07-12, 581J/551J*07-12, 549J*08-09, and 524J: Turn off and lock out unit power.
  • Page 34: Vfd Parameters

    Table 24 — ACH550/580 VFD parameters — 524J Unit units with electromechanical controls VFD parameters for units with VFD fan speed relay board — 524J*07-30A and 524J*07-25H Table 18 — ACS320 VFD Common Parameters for 580J/581J, 551J/558J, 548J and 549J Units with Electromechanical Controls PARAMETERS DESCRIPTION...
  • Page 35 Table 19 — ACS320 VFD Parameters, for 580J/581J, 551J/558J, 548J and 549J Units with Electromechanical Controls VFD PARAMETERS PKG ABB ACS320 MOTOR PART NUMBER VFD PART NUMBER DRIVE HP DESC 48TM003773-DATA 48TM003773 HD56FR233 HK30WA523 SRT 1.7 HP 230V 48TM003776-DATA 48TM003776...
  • Page 36 Table 19 — ACS320 VFD Parameters, for 580J/581J, 551J/558J, 548J and 549J Units with Electromechanical Controls (cont) LOOKUP VARIABLE VOLTAGE N. AMPS N. RPM N. HP MAX AMPS CROSS REFERENCE VFD PARAMETERS 9905 9906 9908 9909 2003 EM_PKG CL_PKG 48TM003773-DATA...
  • Page 37 Table 20 — ACS320 VFD Common Parameters for 524J Units with Electromechanical Controls PARAMETERS DESCRIPTION SETTING ACS320 9802 COMM PROT Sel — 9907 Motor Nominal Frequency 60Hz 1001 EXT1 Commands — 1102 EXT1/EXT2 Sel — 1103 REF 1 Select — 1201 Const Speed Sel DI 2,3...
  • Page 38 Table 21 — ACS320 VFD Parameters, for 524J Units with Electromechanical Controls VFD PARAMETERS PKG ABB ACS320 MOTOR PART NUMBER VFD PART NUMBER DRIVE HP DESC 40RU000130-DATA 40RU000130 HD56FR233 HK30WA523 40RU 1.7 HP 230V 40RU000131-DATA 40RU000131 HD56FR463 HK30WA530 40RU 1.7 HP 460V 40RU480011-DATA 40RU480011 HD56FE653...
  • Page 39 Table 22 — ACH550/580 VFD Common Parameters for 558J/580J and 551J/581J Units with Electromechanical Controls PARAMETERS ACH550 / 580 DESCRIPTION SETTING ACH550 | ACH580 9802 / 58.01 COMM PROT Sel — 9907 / 99.08 Motor Nominal Frequency 60Hz 1001 / 20.01 EXT1 Commands —...
  • Page 40 Table 23 — ACH550/580 VFD Parameters, for 558J/580J and 551J/581J Units with Electromechanical Controls MOTOR DRIVE VFD PARAMETERS PKG ABB ACH550 PART NUMBER DESC PART NUMBER ACH550 / ACH580 48TM482532-DATA 48TM482532 HD56FR233 HK30WA352 / HK30WB304 SRT 1.7 HP 230V 48TM482535-DATA...
  • Page 41 Table 23 — ACH550/580 VFD Parameters, for 558J/580J and 551J/581J Units with Electromechanical Controls (cont) VOLTAGE N. AMPS N. RPM N. HP MAX AMPS LOOKUP VARIABLE CROSS REFERENCE 550/580 550/580 550/580 550/580 550/580 VFD PARAMETERS 9905 / 99.07 9906 / 99.06 9908 / 99.09...
  • Page 42 Table 24 — ACH550/580 VFD Parameters — 524J Unit VFD Parameters for Units with VFD Fan Speed Relay Board — 524J*07-30A and 524J*07-25H 550 / 580 550 / 580 NOM 550 / 580 550 / 580 550/580 VFD PART 550/580 ABB PART MOTOR PART 550/580 VOLT MOTOR NOM...
  • Page 43 Table 24 — ACH550/580 VFD Parameters — 524J Unit VFD Parameters for Units with VFD Fan Speed Relay Board — 524J*07-30A and 524J*07-25H (cont) 550 / 580 550 / 580 550 / 580 550 / 580 550 / 580 550 / 580 550/580 VFD PART 550/580 ABB PART CONST SPEED...
  • Page 44 Table 24 — ACH550/580 VFD Parameters — 524J Unit VFD Parameters for Units with VFD Fan Speed Relay Board — 524J*07-30A and 524J*07-25H (cont) 550 / 580 550 / 580 550 / 580 550 / 580 550 / 580 550 / 580 550 / 580 550 / 580 550 / 580...
  • Page 45: Vfd Remote Keypad

    KIT003A00) ACH580. of start-up assistant will override the factory VFD configurations. On 548J/549J, 551J/558J and 580J/581J Series single package rooftop units and 524J fan coils equipped with the 2-Speed Indoor START UP BY CHANGING PARAMETERS Fan Motor option, the supply fan speed is controlled by a 3-phase INDIVIDUALLY VFD.
  • Page 46 To view the default parameter value, press the UP and Select EXIT (SOFT KEY 1) to return to the main menu. DOWN keys simultaneously. To restore the default factory set- The control panel can now be disconnected from the drive. tings, select the Bryant application macro.
  • Page 47: Ach550/Acs320 Vfd Diagnostics

    Download Application Parameters ACH550/ACS320 VFD Diagnostics To download application parameters only to the control panel The drive detects error situations and reports them using: from the VFD, perform the following procedure: • Green and red LEDs on the body of the drive (located un- Install the control panel with the correct parameters onto der the keypad) the VFD.
  • Page 48 3015 UNDERLOAD CURVE. THERM FAIL Internal fault. The thermistor measuring the internal temperature of the drive is open or shorted. Contact Bryant. OPEX LINK Internal fault. A communication-related problem has been detected between the OMIO and OINT boards. Contact Bryant.
  • Page 49 Table 25 — ACH550/ACS320 Fault Codes (cont) FAULT FAULT NAME IN PANEL DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION CODE Parameter values are inconsistent. Check that parameter 1301 AI 1 MIN > 1302 AI 1 MAX and that parameter 1304 AI 2 1003 PAR AI SCALE MIN >...
  • Page 50: Reset After Using Start-Up Assistant

    Reset After Using Start-Up Assistant Use the following procedure to reset the factory configurations for ACH550 VFDs: Disconnect unit power. Lock-out/tag-out. CAUTION Remove the VFD’s front cover (see Fig. 39 on page 30). Disconnect the DI1 input at Terminal 13 (see Fig. 56 for CONFIGURATION OVERRIDE HAZARD location of DI1).
  • Page 51: Ach580 Operation With Remote Keypad

    ACH580 Operation with Remote Keypad The VFD keypad is shown in Fig. 57 and Fig 58. The functions of CAUTION the Left and Right Softkeys ( ) change depending on what is displayed on the screen. The function of Left Softkey CONFIGURATION OVERRIDE HAZARD matches the word in the lower left-hand box on the display screen.
  • Page 52: Ach580 Vfd Modes

    START UP BY CHANGING PARAMETERS The bottom corners of the LCD display show the functions cur- rently assigned to the two soft keys. The lower middle displays the INDIVIDUALLY current time (if configured to show the time). Initial start-up is performed at the factory. To start up the VFD by The first time the drive is powered up, it is in the OFF mode.
  • Page 53 PARAMETERS MODE The second option downloads only the application parameters to the drive. This is recommended when using the same application The Parameters mode is used to change the parameters on the for drives of different sizes. Parameters 99.07, 99.06, 99.08, 99.09, drive.
  • Page 54: Ach580 Vfd Diagnostics

    Use the UP or DOWN keys to change the parameter setting. If diagnostics troubleshooting has determined that the drive is de- Press SAVE (Press ). to save the configuration. Press fective during the warranty period, contact Bryant.
  • Page 55 Hardware manual of the drive. If an earth fault is found, fix or change the motor cable and/or motor. If no earth fault can be detected, contact your local Bryant representative. Check motor and motor cable for cabling errors.
  • Page 56 Table 27 — Fault and Alarm Codes for ACH580 VFD (cont) CODE (HEX) WARNING / AUX. CODE CAUSE WHAT TO DO The start delay is active and the Check that it is safe to continue operation. Then return AFE9 Start delay drive will start the motor after a emergency stop push button to normal position.
  • Page 57: All Ach580, Ach550 And Acs320 Keypads

    HD60FE576 60Hz 1725 40Hz 60Hz 60Hz NOTE(S): a. ACH580 values shown. ACH550 1201 value = DI2,3 Table 29 — ACH550/580 VFD Parameters — 558J/580J*07-14, 548J*07-12, 551J/581J*07-12 and 549J*08-09 (cont) ACH550 ACH580 Switch Stop Accel/ Relay Out 3 Start Fcn Accel...
  • Page 58 HD60FL576 60Hz 1745 40Hz 60Hz 60Hz NOTE(S): a. ACH580 values shown. ACH550 1201 value = DI2,3 Table 31 — ACH550/580 VFD Parameters — 558J/580J*16, 548J*14, 551J/581J*14 and 549J*12 (cont) ACH550 ACH580 Switch Stop Accel/ Relay Out 3 Start Fcn Accel...
  • Page 59 Table 32 — ACH550/580 VFD Parameters — 558J/580J*17-30, 548J*17-24 and 551J/581J*17-28 Motor Const Const Const Const Const ACH550 ACH580 Voltage Speed Speed Speed Speed Speed VFD Part Replacement Replacement Motor Part Amps Description 9905 Freq Number Component Component Number 9906...
  • Page 60 Table 33 — ACH550/580 VFD Parameters — 558J/580J*17-30, 548J*17-24 and 551J/581J*17-28 (cont) ACH550 ACH580 Switch Stop Accel/ Relay Out 3 Start Fcn Accel Decel VFD Part Replacement Replacement Amps Freq Freq Freq Decel Description 1403 2101 2202 2203 Number Component...
  • Page 61 Table 34 — ACH550/580 VFD Parameters — 524J*07-30A and 524J*07-25H Motor Const Const Const Const Const ACH550 ACH580 Volt Speed Speed Speed Speed Speed VFD Part Replacement Replacement Motor Part Amps Description (9905/ Freq Number Component Component Number (9906/ (9909/ 99.07) (9907/ (9908)
  • Page 62 STR 5.0 HP 460V HD60FK657 60 Hz 1760 DI 2,3 40 Hz 60 Hz 60 Hz Table 37 — ACS320 VFD Parameters — 558J/580J*07-16 and 548J*07-14 (208/230V and 460V units only) (cont) Replacement Relay Out Switch Start Stop Accel/ VFD Part Motor Part...
  • Page 63 15.2 60 Hz 1755 10.0 DI 2,3 40 Hz 60 Hz 60 Hz Table 39 — ACS320 VFD Parameters — 558J/580J*17-30 and 548J*17-24 (208/230V and 460V units only) (cont) Replacement Relay Out Switch Start Stop Accel/ VFD Part Motor Part...
  • Page 64 Table 40 — ACS320 VFD Parameters — 524J (208/230V and 460V units only) Motor Const Const Const Const Replacement VFD Part Motor Part Volt Speed Speed Speed Speed Component Part Description Amps Number Number (9905) Freq Number (9906) (9908) (9909) (9907) (1201) (1202)

This manual is also suitable for:

558j548j581j551j549j

Table of Contents