Illusion Aussie Made LCSII-LUMINAR Series Manual page 5

Gas log fires

Advertisement

A1
B1
Minimum
Width of
Frameout
300mm
min
Model
A1
B1
1000
765mm
540mm
2000
865mm
585mm
3000
965mm
635mm
4000
1330mm
620mm
Plaster cut out sizes. (Suits Standard fascia)
IMPORTANT: If an inbuilt unit is installed at floor level, or up to 600mm
from the underside of the appliance door, a hearth should be used for a
distance of 400mm in front of the appliance. The appliance should be
installed 600mm or more from the floor if no hearth is used.
Luminar Model
PLASTER CUTOUT
HEIGHT (MUST BE
ACCURATE)
1000
510mm
2000
555mm
3000
595mm
4000
590mm
All dimensions for the Illusion Luminar series of Gas Log Fires are correct at the time of printing. It is always advisable to
check dimensions and clearances with your Illusion dealer before commencing installation thus avoiding potential
problems during the installation.
INSTALLER INFORMATION
READ THIS BEFORE CUTTING
ANY HOLES IN PLASTER OR
OTHER WALLS
IMPORTANT!
The plaster cut out must be
straight and accurate, especially
at the bottom. There is no overlap
of the fascia at the bottom so the
bottom plaster edge must be cut
carefully. It is recommended that
a plaster trim strip be fitted.
Australian Made Gas Log Fires
LUMINAR INBUILT INSTALLATION
The Illusion Luminar Gas Log Fires
have been designed for simple
installation through an existing
wall (external or internal). They
can also be installed into a
purpose built enclosure or an
existing suitably large chimney.
The diagram at left shows an
example of an enclosure which
would attach to an existing
internal wall. The enclosure
can be plastered or faced
with a variety of materials
C1
including tiles or stone and other
decorative masonary products.
C1
The enclosure should be a
440mm
minimum of 300mm wider than
440mm
the hole cut out. Check with
your dealer for more detailed
440mm
information.
440mm
PLASTER CUTOUT
MIN. DEPTH OF
WIDTH
FRAMEOUT
705mm
450mm
805mm
450mm
905mm
450mm
1270mm
450mm
EXAMPLE VERTICAL AND HORIZONTAL
Minimum
from flue cowl
exit to roof
penetration
p p e
Clear path to vent
Minimum
distance
from flue
case outer
pipe to
combustible
materials is
10mm
INBUILT CLEARANCES
Minimum distance from top
of unit to any combustible
framing is 50mm.
Minimum distance from rear
of unit to any combustible
material is 10mm.
Minimum distance from side
of unit to any combustible
material is 50mm
Appliance
Fascia
PLASTER
FASCIA
5
INSTALL VERSIONS
500mm
Approved
Vertical
Flue Cowl
air to ceiling
Stud Wall
Flue Pipe
100mm
(4")
Active &
152mm
(6")
Outer
Horizontal
or Vertical
Flue
Luminar
Gas Log
Fire
WALL STUD
LUMINAR
INBUILT
LCSII-LUMINAR SERIES OCT 2015
Flashing
(Supplied
by
Installer)
ALL LUMINAR GAS
LOG FIRES MUST BE
INSTALLED IN
ACCORDANCE WITH
AS-NZS 5601
CURRENT EDITION