If the field
"On
Timer" is checked, the IEC61850 variable is sent/read cyclically;
In the field
"Time
(ms)" the delay in ms between two readings/writings of the variable is defined (if "On Timer" is checked);
In the field "Position" the starting byte of the internal memory arrays where saving/getting the value is defined;
In the field
"Start
Bit" the starting bit of the byte of the field "Position" is defined (only for BOOLEAN data);
In the field "R/W" the access type of the IEC61850 variable is defined;
In the field "Conversion" the type of conversion of the value is defined (only for FLOAT32/FLOAT64 data);
In the field
"Molt
Fact" the multiplication factor for the conversion is defined (if "Conversion" is defined as "ItoF/FtoI");
In the field "Mnemonic" a description of the variable is defined.
Note:
Not all variables can be written. It depends on their Functional Constraints (fc).
ADFweb.com Srl – IT31010 – Mareno – Treviso
User Manual IEC61850 Client / BACnet Slave
Document code: MN67767_ENG
Revision 1.000