Parameter Table

This parameter table shows the most important parameters. Default settings are in bold type. Refer to the Technical Manual
for a complete list of parameters.
No.
Name
A1-03
Initialize Parameters
A1-06
Application Preset
Frequency Reference
b1-01
Selection 1
Run Command
b1-02
Selection 1
Stopping Method
b1-03
Selection
Reverse Operation
b1-04
Selection
Speed Search Selection
b3-01
at Start
Speed Search Method
b3-24
Selection
Energy Saving Control
b8-01
Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
C1-03
Acceleration Time 2
C1-04
Deceleration Time 2
C1-09
Fast-Stop Time
Accel/Decel Time
C1-10
Setting Units
Accel/Decel Time
C1-11
Switching Frequency
S-Curve Characteristic
C2-01
at Accel Start
S-Curve Characteristic
C2-02
at Accel End
S-Curve Characteristic
C2-03
at Decel Start
S-Curve Characteristic
C2-04
at Decel End
YASKAWA ELECTRIC TOEP YAIP1U 03B YASKAWA AC Drive – P1000 Safety Precautions
Description
0: No initialization
1110: User Initialize (parameter values
must be stored using parameter o2-03)
2220: 2-Wire initialization
3330: 3-Wire initialization
5550: oPE04 error reset
8008: Pump
8009: Pump w/ PI
8010: Fan
8011: Fan w/ PI
0: General-purpose
8: Pump
9: Pump w/PI
10: Fan
11: Fan w/PI
Note: This parameter is not settable. It is
used as a monitor only.
0: Digital operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse input (terminal RP)
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
0: Ramp to stop
1: Coast to stop
2: DC Injection Braking to stop
3: Coast with timer
0: Reverse enabled.
1: Reverse disabled.
0: Disabled
1: Enabled
0: Current Detection
1: Speed Estimation
0: Disabled
1: Enabled
Sets the time to accelerate from 0 to
maximum frequency.
Sets the time to decelerate from maximum
frequency to 0.
Sets the time to accelerate from 0 to
maximum frequency.
Sets the time to decelerate from maximum
frequency to 0.
Sets the time for the Fast Stop function.
0: 0.01 s (0.00 to 600.00 s)
1: 0.1 s (0.0 to 6000.0 s)
Sets the frequency to switch between accel/
decel time settings
S-curve at acceleration start.
S-curve at acceleration end.
S-curve at deceleration start.
S-curve at deceleration end.
No.
Name
Carrier Frequency
C6-02
Selection
d1-01 to
Frequency Reference 1
d1-16
to 16
Jog Frequency
d1-17
Reference
Frequency Reference
d2-01
Upper Limit
Frequency Reference
d2-02
Lower Limit
E1-01
Input Voltage Setting
E1-03
V/f Pattern Selection
Maximum Output
E1-04
Frequency
E1-05
Maximum Voltage
E1-06
Base Frequency
Middle Output
E1-07
Frequency
Middle Output
E1-08
Frequency Voltage
Minimum Output
E1-09
Frequency
Minimum Output
E1-10
Frequency Voltage
Middle Output
E1-11
Frequency 2
Middle Output
E1-12
Frequency Voltage 2
E1-13
Base Voltage
E2-01
Motor Rated Current
i.6 Parameter Table
Description
1: 2.0 kHz
2: 5.0 kHz (4.0 kHz)
3: 8.0 kHz (6.0 kHz)
4: 10.0 kHz (8.0 kHz)
5: 12.5 kHz (10.0 kHz)
6: 15.0 kHz (12.0 kHz)
7: Swing PWM1 (Audible sound 1)
8: Swing PWM2 (Audible sound 2)
9: Swing PWM3 (Audible sound 3)
A: Swing PWM4 (Audible sound 4)
B to E: No setting possible
F: User-defined (determined by C6-03
through C6-05)
Sets the frequency reference for the drive.
Setting units are determined by parameter
o1-03.
Sets the Jog frequency reference. Setting
units are determined by parameter o1-03.
Sets the frequency reference upper limit as
a percentage of the maximum output
frequency.
Sets the frequency reference lower limit as
a percentage of the maximum output
frequency.
This parameter must be set to the power
supply voltage.
0: 50 Hz, Constant torque 1
1: 60 Hz, Constant torque 2
2: 60 Hz, Constant torque 3 (50 Hz base)
3: 72 Hz, Constant torque 4 (60 Hz base)
4: 50 Hz, Variable torque 1
5: 50 Hz, Variable torque 2
6: 60 Hz, Variable torque 1
7: 60 Hz, Variable torque 2
8: 50 Hz, High starting torque 1
9: 50 Hz, High starting torque 2
A: 60 Hz, High starting torque 3
B: 60 Hz, High starting torque 4
C: 90 Hz (60 Hz base)
D: 120 Hz (60 Hz base)
E: 180 Hz (60 Hz base)
F: Custom V/f, E1-04 through E1-13
settings define the V/f pattern
These parameters are only applicable when
E1-03 is set to F.
To set linear V/f characteristics, set the
same values for E1-07 and E1-09.
In this case, the setting for E1-08 will be
disregarded. Ensure that the four
frequencies are set according to these rules:
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
Output Voltage (V)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
E1-07 E1-06 E1-11 E1-04
Frequency (Hz)
Sets the motor nameplate full load current
in amps. Automatically set during
Auto-Tuning.