4-2 Muting function

Muting and Override function can disable the safety functions of a machine. The
proper installation, checkout and operation of a machine and muting system in
accordance with all applicable laws and standards, is critical to the safe operation
of the machine.
Failure to comply with these instructions may result in severe injury to personnel.
Muting sensors must be positioned so that they cannot be activated inadvertently
by personnel.
The muting lamp for indication "active muting" or "active override" must be
positioned in a place where it can be seen from any operative point.

4-2-1 Installation Criteria

1
The muting sensors must recognise the material (namely pallets,
vehicles, etc.) over its full length.
2
The sensors must be arranged in such a way that the material is
recognised even when it is on a pallet or other transporting medium.
3
In case of different transport speeds through the muting area,
consideration must be used on the muting duration.
Section 4 Operation
WARNING
17