Section 2 Wiring and Mounting

2-2 Mounting

Mount the F3SP on DIN rail with 35mm width.
■When Mounting;
Hang the one end of DIN rail to
the F3SP, and push the F3SP
until it is locked.

2-3 Wiring

Always use the two OSSD outputs to configure the safety system.
Using only one OSSD of the safety system may result in serious injury when there
is an output circuit failure.
Do not connect the F3SP to AC or DC power supply with higher voltage then
nominal 24VDC.
[Note]: Make sure to connect the muting lamp, otherwise the F3SP is locked.
[Note]: Use the following to wire the F3SP.
-
Wire size: 14 – 24 AWG, Solid / Stranded wire
-
Wire type: copper (Cu) conductor
Appropriate terminal tightening torque: 2 N m
The cable shield braids must be all earthed on the F3SP side.
[Note]: Be sure to route the F3SP cable separately from high-potential power lines or
through an exclusive conduit.
8
■When Unmounting;
Pull out the hook located at the
bottom of F3SP, using screw
driver.
WARNING