Section 4 Operation; Dip-Switches Configuration - Omron F3SP-U2P Instruction Manual

Muting controller
Hide thumbs Also See for F3SP-U2P:
Table of Contents

Advertisement

Section 4 Operation

Section 4 Operation

4-1 Dip-switches configuration

Configuration of dip switch is must only carries out by qualified person.
The configuration shown in the table below must be selected on both sets of dip-
switches on the internal board. The description corresponding to the pre-chosen
selection is shown below.
To configure dip-switch, remove the lateral plastic cover with screwdriver.
No.
ON/OFF
1
X
2
OFF
ON
3
OFF
ON
4
OFF
ON
[Note]: While the F3SP is connected to power, do not change any dip switch to avoid
influence on the system safety.
16
FUNCTION
not used
Muting A-B act on the light curtain 1
Muting C-D act on the light curtain 2
(default setting)
Forbidden
Muting 60 seconds (min.)
(default setting)
Muting∞ (infinity)
Manual reset mode
Auto reset mode
(default setting)
WARNING
Note: Configure the two dip switch in the
Note: SW2 is mounted upside down
same way, otherwise code '8' is
displayed, which means a failure.
against SW1.