MAKE WIRE LEAD CONNECTIONS INSIDE THE JUNCTION BOX
3
1.
Make all wire connections by using appropriate UL-listed electrical connectors and techniques.
2.
Select the applicable wiring situation and follow the instructions accordingly:
• 1-Phase 220-240 VAC
When connecting the Zoneline to a single-phase circuit
for 230V applications:
Connect the white and black leads of the Zoneline
power supply kit to the branch circuit L1 and L2 leads.
(The white lead of the power supply kit should be
identified by the installer using electrical tape with some
color other than green or white.) Connect the green lead
of the power supply kit to the power supply and branch
circuit ground.
• 3-Phase 208 VAC
When connecting the Zoneline to a three-phase circuit
for 208V applications:
Connect the white and black leads of the Zoneline
power supply kit to the branch circuit L1 and L2 leads.
(The white lead of the power supply kit should be
identified by the installer using electrical tape with some
color other than green or white.) Connect the green lead
of the power supply kit to the power supply and branch
circuit ground.
3.
Be sure that all wire leads are inside the junction box and not
pinched between the box and the unit. The green insulated
ground wire from the Zoneline MUST be connected to the branch
circuit ground wire.
4.
Plug the 9-pin connector into the 9-pin receptacle in the junction box.
5.
Replace the junction box cover by replacing the two screws
removed earlier.
POWER CONNECTION CHART
230/208 Volt
Power Supply Kits
RAK3152
RAK3202
RAK3302
230/208 Volt
Power Supply Kits
RAK4157
RAK4207
RAK4307
265 Volt
Power Supply Kits
RAK5157
RAK5207
RAK5307
Installation Instructions
DIRECT CONNECT APPLICATIONS
Power Cord Connections
Wall Plug
Configuration
Tandem
15-Amp Time-Delay Fuse or Breaker
Perpendicular
20-Amp Time-Delay Fuse or Breaker
Large Tandem
30-Amp Time-Delay Fuse or Breaker
Direct Connections
Heater Wattage
@ 230/208 Volts
2.55 KW/2.09 KW
3.45 KW/2.82 KW
5.00 KW/4.10 KW
Heater Wattage
@ 265 Volts
2.55 KW
3.45 KW
5.00 KW
• 3-Phase 208 VAC with "Crazy Leg"
When connecting the Zoneline to a three-phase circuit
with "Crazy Leg" for 208V applications:
Connect the white and black leads of the Zoneline
power supply kit to the branch circuit Neutral and L1
leads. (The white lead of the power supply kit should
be connected to neutral.) Connect the green lead of
the power supply kit to the power supply and branch
circuit ground.
• 3-Phase 253-277 VAC
When connecting the Zoneline to a three-phase circuit
for 265V applications:
Connect the white and black leads of the Zoneline
power supply kit to the branch circuit Neutral and L1
leads. (The white lead of the power supply kit should
be connected to neutral.) Connect the green lead of
the power supply kit to the power supply and branch
circuit ground.
Circuit Protective Device
Circuit Protective Device
15-Amp Time-Delay Fuse or Breaker
20-Amp Time-Delay Fuse or Breaker
30-Amp Time-Delay Fuse or Breaker
Circuit Protective Device
15-Amp Time-Delay Fuse or Breaker
20-Amp Time-Delay Fuse or Breaker
30-Amp Time-Delay Fuse or Breaker
13
Conduit
Make wire lead
connections
Heater Wattage
@ 230/208 Volts
2.55/2.09 KW
3.45/2.82 KW
5.00/4.10 KW