Remote control relay control module (do 8 points, tension clamp terminal block)

Advertisement

WIRING INSTRUCTIONS

■ APPLICABLE WIRE SIZE
• Solid: 0.2 to 1.0 mm
(0.55 to 1.12 dia.)
2
• Stranded: 0.2 to 1.5 mm
2
(Tinning wire ends may cause contact failure and therefore
is not recommended.)
• Ferruled:
Unsheathed: 0.25 to 1.5 mm
Sheathed: 0.25 to 0.75 mm
• Expose wire conductors by 10 mm (0.39").
Stripped length
10mm
■ CONNECTION PROCEDURE
Insert the wire end until it comes to a full stop while push-
ing slot with the tip of a screw driver as shown below. Be
sure wire insulation is not inside the terminal.
2
2
Screw Driver
Power wire
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp