M-system R3-SV8B Instruction Manual

Dc voltage input module

Advertisement

Quick Links

INSTRUCTION MANUAL
DC VOLTAGE INPUT MODULE
(8 points, isolated, wide span voltage)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
DC voltage input module ............................................. (1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
MODEL
POINTS OF CAUTION
■ HOT INSERTION/REMOVAL OF MODULES
Removing or replacing modules does not affect other mod-
ules on the same backplane. It is possible to replace them
without removing the power supply. However, replacing
multiple modules at once may greatly change line voltage
levels. We recommend that you replace them one by one.
■ ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ven-
tilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables (power supply, input and output)
close to noise sources (relay drive cable, high frequency
line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ UNUSED INPUT CHANNELS
Set the unused channels to -30 – +30V range. Otherwise, set
them as "Unused" with PC Configurator software: R3CON.
Unused channels left open with other settings may be equal
to the input lower than -15%, which sets a data abnormality
at the PLC or the host device.
■ AND ....
The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for sat-
isfying complete performance described in the data sheet.
INSTALLATION
Use the Installation Base (model: R3-BSx).
R3-SV8B
R3-SV8B
EM-844 Rev.2
P.  / 3

Advertisement

loading

Summary of Contents for M-system R3-SV8B

  • Page 1 BEFORE USE ..POINTS OF CAUTION ■ HOT INSERTION/REMOVAL OF MODULES Thank you for choosing M-System. Before use, please check Removing or replacing modules does not affect other mod- contents of the package you received as outlined below. If you have any problems or questions with the product, ules on the same backplane.
  • Page 2 R3-SV8B COMPONENT IDENTIFICATION ■ SIDE VIEW ■ FRONT VIEW RUN LED ERR LED Functions Range Conv. Input 1-4 (SW1) Rate Input 5-8 (SW2) ■ STATUS INDICATOR LED RUN indicator: Bi-color (red/green) LED; Red when the bus A operates normally; Green when the bus B operates normally;...
  • Page 3 M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.