INSTRUCTION MANUAL
DC VOLTAGE INPUT MODULE
(8 points, isolated, wide span voltage)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
DC voltage input module ....................................................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
MODEL
POINTS OF CAUTION
■ HOT SWAPPABLE MODULES
• Replacing the module does not affect other modules on
the same base. Thus, the module can be replaced while
the power is ON. However, replacing multiple modules
at once may greatly change live voltage levels. We highly
recommend to replace them one by one.
■ GENERAL PRECAUTIONS
• DO NOT set the switches on the module while the power
is supplied. The switches are used only for maintenance
without the power.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ UNUSED INPUT CHANNELS
• Set the unused channels to open. Otherwise, set them as
"Unused" with PC Configurator software: R3CON.
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
INSTALLATION
Use the Installation Base (model: R3-BSx).
R3-SV8B
EM-8414 Rev.5 P. 1 / 3

Advertisement

loading

Summary of Contents for M-system R3-SV8B

  • Page 1 (8 points, isolated, wide span voltage) BEFORE USE ..POINTS OF CAUTION Thank you for choosing M-System. Before use, please check ■ HOT SWAPPABLE MODULES contents of the package you received as outlined below. • Replacing the module does not affect other modules on If you have any problems or questions with the product, the same base.
  • Page 2 -32000 to +32000 10000 Zero Adjust -320.00 to +320.00 0.00 Full Adjust -32000 to +32000 1.0000 Unused 0: Enable 0: Enable 1: Disable EM-8414 Rev.5 P. 2 / 3 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 3 12max – (mm) INPUT 7 – INPUT 8 – *For dual redundant communication. DO NOT connect external wiring to the unused terminals. EM-8414 Rev.5 P. 3 / 3 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...