M-system R3-NL1 Instruction Manual

Lonworks interface module (analog i/o 16 points, discrete i/o 48 points)
Hide thumbs Also See for R3-NL1:

Advertisement

Quick Links

INSTRUCTION MANUAL
L
W
ON
ORKS
(analog I/O 16 points, discrete I/O 48 points)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Network interface module ..................................................(1)
Neuron ID label ...................................................................(2)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ HOT SWAPPABLE MODULES
• The module can be replaced while the power is ON. Be
sure to replace it when the module is not communicat-
ing with a host, as it may affect the system. Replacing
multiple modules at once may greatly change line voltage
levels. We highly recommend to replace them one by one.
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 120V AC rating: 85 – 132V, 47 – 66 Hz, approx. 20VA
200 – 240V AC rating: 170 – 264V, 47 – 66 Hz, approx. 20VA
24V DC rating: 24V ±10%, approx. 12W
■ GENERAL PRECAUTIONS
• DO NOT set the switches while the power is supplied.
The switches are used only for maintenance without the
power.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
INTERFACE MODULE
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
MODEL
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
INSTALLATION
Use the Installation Base Model R3-BS, or Model R3-BSW
for free I/O address capability.
Before mounting the Network Interface Module onto the
base, be sure to configure the module as explained below.
■ DATA ALLOCATION
The setting determines the data area size assigned to each
I/O module mounted on the base.
■ NETWORK SLOTS ON THE BASE
I/O 1
I/O 2
With Model R3-BS base, mount the I/O Modules from the
left end (I/O 1) to the right in order that the Network Mod-
ule assigns data areas from I/O 1.
Network Module(s) and Power Module are mounted basi-
cally at the right end though technically they could be
mounted in any position.
With Model R3-BSW base, there is no limitation in mount-
ing positions as I/O address can be assigned freely to each
module using rotary switches equipped on the base.
R3-NL1
I/O n
EM-8427 Rev.7 P. 1 / 9

Advertisement

Table of Contents
loading

Summary of Contents for M-system R3-NL1

  • Page 1 • The unit is designed to function as soon as power is sup- plied, however, a warm up for 10 minutes is required for Thank you for choosing M-System. Before use, please check satisfying complete performance described in the data contents of the package you received as outlined below.
  • Page 2: Component Identification

    OFF (*) Green when normal Green when abnormal Red when receiving Red when transmitting Note: Be sure to set unused SW3-3 to OFF. EM-8427 Rev.7 P. 2 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 3: Terminal Connections

    (mm) ■ EURO TYPE CONNECTOR TERMINAL (L ORKS Applicable wire size: 0.2 to 2.5 mm (AWG24 to 12) Stripped length: 7 mm EM-8427 Rev.7 P. 3 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 4: Communication Cable Connections

    Terminator I/O COMBINATIONS A dedicated Device File for each I/O device depending upon I/O combinations is required to set up the R3-NL1 using an inte- gration tool such as LonMaker. On-line download is available for Device Image files at http://www.m-system.co.jp/.
  • Page 5: Functional Blocks

    : (identical to nvoVal) Zero value cpNvoSndDelta : (identical to nvoVal) Value deviation to be sent cpNvoType : SCPTnvType Network variable type, etc. EM-8427 Rev.7 P. 5 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 6 R3Di [X] nvoDich01 nvoDich16 SNVT_switch nvoDiState SNVT_state ■ DISCRETE OUTPUT FUNCTIONAL BLOCKS (R3Do [0] through [2]) R3Do [X] nviDoch01 nvoDoState nviDoch16 SNVT_state SNVT_switch EM-8427 Rev.7 P. 6 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 7 Minimum sending time intervals of nvoVal [0 – 15] {0.0 through 6653.4} This minimum time intervals is maintained even when the input {0.0} signals changes faster than it. EM-8427 Rev.7 P. 7 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 8 {100.0} cpNviMinRnge Identical to nviVal nviVal value at 0% output { (Identical to nviVal) } Invalid when nviVal type is SNVT_state. {0.0} EM-8427 Rev.7 P. 8 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 9 When the data consist of only inputs or outputs, data for the total of 16 Functional Blocks (GetValue [0 – 15] or R3Di [0 – 2], or SetValue [0 – 15] or R3Do [0 – 2]) are assigned to each module position from Slot 1. EM-8427 Rev.7 P. 9 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...

Table of Contents