M-system R3S-RS4A Instruction Manual

Rtd input module

Advertisement

Quick Links

INSTRUCTION MANUAL
RTD INPUT MODULE
(high accuracy, 4 points, isolated)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
RTD input module ........................................................ (1)
■ MODEL NO.
Confirm that the model number described on the product is
exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
COMPONENT IDENTIFICATION
FRONT VIEW
RUN LED
ERR LED
SIDE VIEW
1
20
MODEL
POINTS OF CAUTION
■ HOT INSERTION/REMOVAL OF MODULES
Removing or replacing modules does not affect other mod-
ules on the same backplane. It is possible to replace them
without removing the power supply. However, replacing
multiple modules at once may greatly change line voltage
levels. We recommend that you replace them one by one.
■ ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ven-
tilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables (power supply, input and output)
close to noise sources (relay drive cable, high frequency
line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for sat-
isfying complete performance described in the data sheet.
INSTALLATION
Use the Installation Base (model: R3-BSx).
SW3
Conv.
4
Rate
3
Temp.
2
Unit
1
Burnout
ON
R3S-RS4A
R3S-RS4A
SW1
SW2
RTD
8
8
Input 2 (SW1)
7
7
or
6
6
Input 4 (SW2)
5
5
4
4
Input 1 (SW1)
3
3
or
2
2
Input 3 (SW2)
1
1
ON
ON
EM-8936
P. 1 / 3

Advertisement

loading

Summary of Contents for M-system R3S-RS4A

  • Page 1 (high accuracy, 4 points, isolated) BEFORE USE ..POINTS OF CAUTION Thank you for choosing M-System. Before use, please check ■ HOT INSERTION/REMOVAL OF MODULES contents of the package you received as outlined below. Removing or replacing modules does not affect other mod- If you have any problems or questions with the product, ules on the same backplane.
  • Page 2 R3S-RS4A ■ INDICATORS RUN indicator: Bi-color (red/green) LED; Red when the bus A operates normally; Green when the bus B operates normally; Amber when both buses operate normally. ERR indicator: Bi-color (red/green) LED; Red with the in- put abnormality; Green in normal operating conditions. ■ SIDE DIP SW • RTD Type: SW1, SW2 INPUT 1 (SW1) INPUT 2 (SW1) INPUT 3 (SW2) INPUT 4 (SW2) Pt 100 (*) (JIS ’97, IEC) Pt 100 (JIS ’89) JPt 100 Pt 1000 • Burnout: SW3 •...
  • Page 3 M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.