INSTRUCTION MANUAL
CC-Link INTERFACE MODULE
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
the contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
PACKAGE INCLUDES:
Network interface module .......................................... (1)
Terminating resistor (110Ω, 0.25W) .......................... (1)
MODEL NO.
Check that model No. described on the specification label is
exactly what you ordered.
INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, including installation, connection and basic
maintenance procedures.
POINTS OF CAUTION
CONFORMITY WITH EC DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrated in
a panel system.
The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
POWER INPUT RATINGS
Operational range & power consumption: Check the power
rating for the unit on the specification label.
Rating 100 – 120V AC: 85 – 132V, 47 – 66 Hz, approx. 20VA
Rating 200 – 240V AC: 170 – 264V, 47 – 66 Hz, approx. 20VA
Rating 24V DC: 24V ±10%, approx. 12W
UNPLUGGING THE UNIT
Before you remove the unit from its base or mount it, turn off
the power supply for safety.
ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ventila-
tion.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH in
order to ensure adequate life span and operation.
WIRING
• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present. Do not install them in the same duct.
(CC-Link Ver.2)
MODEL
AND ....
The unit is designed to function as soon as power is supplied,
however, a warm up for 10 minutes is required for satisfying
complete performance described in the data sheet.
INSTALLATION
Use the Installation Base Model R3-BSx, or Model R3-BSWx
for free I/O address capability.
Before mounting the Network Interface Module onto the
Base, be sure to configure the module as explained below.
DATA ALLOCATION
The setting determines the data area size assigned to each I/
O module mounted on the base.
The data sent/received via CC-Link is mapped according to
this setting.
See "DATA DESCRIPTION" in Page 4.
NODE ADDRESS & BAUD RATE
See "COMPONENT IDENTIFICATION" in Page 2.
NETWORK SLOTS ON THE BASE
I/O 1
I/O 2
With Model R3-BSx base, mount the I/O Modules from the
left end (I/O 1) to the right in order that the Network Module
assigns data areas from I/O 1.
Network Module(s) and Power Module are mounted basically
at the right end though technically they could be mounted in
any position.
With Model R3-BSWx base, there is no limitation in mount-
ing positions as I/O address can be assigned freely to each
module using rotary switches equipped on the base.
R3-NC3
R3-NC3
I/O n
P. 1 / 7
EM-8422 Rev.9

Advertisement

loading

Summary of Contents for M-system R3-NC3

  • Page 1 The unit is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for satisfying Thank you for choosing M-System. Before use, please check complete performance described in the data sheet. the contents of the package you received as outlined below.
  • Page 2: Component Identification

    R3-NC3 COMPONENT IDENTIFICATION FRONT VIEW SIDE VIEW Node Address Rotary SW RUN LED B RATE Baud Rate Rotary SW ERR LED Functions Configuration Jack Terminal Block BAUD RATE ROTARY SW SW POSITION BAUD RATE 156 kbps 625 kbps 2.5 Mbps...
  • Page 3: Terminal Connections

    R3-NC3 TERMINAL CONNECTIONS Connect the unit as in the diagrams below. DIMENSIONS mm (inch) 27.5 (1.08) 109 (4.29) POSITIONING GUIDE 6–M3 SCREW TERMINAL COVER CONNECTION DIAGRAM WIRING INSTRUCTIONS SOLDERLESS TERMINAL mm (inch) Refer to the drawing below for recommended ring tongue INTERNAL terminal size.
  • Page 4 Module 6 Module 6 Module 7 Module 7 +16*m–1 +16*m–1 [16*m] (m = cyclic expansion setting) data areas are available to the R3-NC3. Total data areas occupied by I/O modules must be within this limitation. P. 4 / 7 EM-8422 Rev.9...
  • Page 5 R3-NC3 F E D C B A 9 8 7 6 5 4 3 2 1 RX(n+0) Module Status RX(n+1) Error Status (Burnout Bit) RX(n+2) Data Error Status Unused RX(n+m*7–1) Reserved Bit •Module Status RX(n+0)0 through RX(n+0)F indicate whether individual I/O module are mounted or not. The bit corresponding to the mounted slots turns to "1,"...
  • Page 6 R3-NC3 I/O DATA DESCRIPTIONS MODULE STATUS, ERROR STATUS, DATA ERROR STATUS Shows each module's availability and error status. Module 1 Module 2 Module 3 Module 16 ANALOG DATA (models: R3-SV4, YV4, DS4, YS4 and US4) 16-bit binary data. Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary). Negative percentage is represented in 2's complements.
  • Page 7 M-System's sole liability, and purchaser's exclusive remedies, under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.