Viessmann Vitotronic 100 Installation And Service Instructions Manual page 39

Electronic boiler control unit
Table of Contents

Advertisement

Group 3 "DHW"
(cont.)
Coding in the delivered condition
59:0
Cylinder heating:
Start point: Set value -2.5 K
Stop point: Set value +2.5 K
5b:0
Never adjust
5E:0
With "external blocking" signal:
Circulation pump for cylinder heat-
ing remains in control mode.
5F:0
With "external demand" signal:
Circulation pump for cylinder heat-
ing remains in control mode.
60:20
During DHW heating, the boiler
water temperature is max. 20 K
higher than the set DHW tempera-
ture.
61:0
Circulation pump for cylinder heat-
ing starts subject to boiler water
temperature.
62:10
Circulation pump with max 10 min
run-on time after cylinder heating
63:0
Without auxiliary function for DHW
heating
67:40
For solar DHW heating:
Set DHW temperature 40 °C.
Above the selected set tempera-
ture reheating is suppressed
(DHW heating by the boiler is
blocked).
Group 4 "Solar"
Only in conjunction with solar control module, type
SM1
Coding
Coding in the delivered condition
00:8
The solar circuit pump is switched
on when the collector temperature
exceeds the actual DHW tempera-
ture by 8 K.
01:4
The solar circuit pump is switched
off when the differential between
the collector temperature and the
actual DHW temperature is less
than 4 K.
Possible change
59:1
Start point adjustable from 1 to 10 K
to
below set value.
59:10
5E:1
The circulation pump for cylinder
heating stops.
5E:2
The circulation pump for cylinder
heating starts.
5F:1
The circulation pump for cylinder
heating stops.
5F:2
The circulation pump for cylinder
heating starts.
60:5
The differential between the boiler
to
water temperature and the set DHW
60:50
temperature is adjustable from 5 to
50 K.
61:1
Circulation pump for cylinder heating
starts immediately.
62:0
No circulation pump run-on
62:1
Run-on time adjustable from 1 to
to
15 min
62:15
63:1
Auxiliary function: 1 x daily
63:2
Every 2 days to every 14 days
to
63:14
63:15
2 x daily
67:0
Set DHW temperature adjustable
to
from 0 to 90 °C (limited by boiler-
67:90
specific parameters).
Possible change
00:2
The differential between the actual
to
DHW temperature and the start
00:30
point for the solar circuit pump is ad-
justable from 2 to 30 K.
01:1
The differential between the actual
to
DHW temperature and the stop point
01:29
for the solar circuit pump is adjusta-
ble from 1 to 29 K.
Coding level 2
39