Coding level 2
Group 4 "Solar"
(cont.)
Coding in the delivered condition
02:...
Data dependent on the software
version of solar control module
SM1
03:10
The temperature differential be-
tween the collector temperature
and actual DHW temperature is
regulated to 10 K.
04:4
Controller amplification of speed
control 4 %/K
05:10
Min. speed of the solar circuit
pump 10 % of max. speed
06:75
Max. speed of the solar circuit
pump 75 % of max. possible speed
07:0
Interval function of solar circuit
pump switched off
08:60
The solar circuit pump is switched
off when the actual DHW tempera-
ture reaches the maximum cylinder
temperature (60 °C).
09:130
The solar circuit pump is switched
off if the collector temperature rea-
ches 130 °C (maximum collector
temperature to protect the system
components).
0A:5
Temperature differential for stagna-
tion time reduction (reduction in
the speed of the solar circuit pump
to protect system components and
heat transfer medium) 5 K
0b:0
Frost protection function for solar
circuit switched off
0C:1
Delta T monitoring switched on
No flow rate captured in the solar
circuit, or flow rate too low.
0d:1
Night-time DHW circulation moni-
toring switched on
Unintentional flow rate in the solar
circuit (e.g. at night) is captured.
0E:1
Heat statement in conjunction with
Viessmann heat transfer medium
0F:70
Solar circuit flow rate at maximum
pump speed 7 l/min
40
Possible change
02:0
Solar circuit pump not speed-con-
trolled
02:1
With wave packet control function
Never adjust
02:2
Solar circuit pump speed-controlled
with PWM control
03:5
Temperature differential adjustable
to
from 5 to 20 K
03:20
04:1
Controller amplification adjustable
to
from 1 to 10 %/K
04:10
05:2
Min. speed of solar circuit pump ad-
to
justable from 2 to 100 %.
05:100
06:1
Max. speed of solar circuit pump ad-
to
justable from 1 to 100 %.
06:100
07:1
Interval function of solar circuit pump
switched on
To capture the collector temperature
more accurately, the solar circuit
pump periodically starts for a short
duration.
08:10
Set DHW temperature adjustable
to
from 10 to 90 °C.
08:90
09:20
Temperature adjustable from 20 to
to
200 °C.
09:200
0A:0
Stagnation time reduction is disa-
bled.
0A:1
Temperature differential adjustable
to
from 1 to 40 K.
0A:40
0b:1
Frost protection function for solar cir-
cuit switched on (not required with
Viessmann heat transfer medium)
0C:0
Delta T monitoring switched off
0d:0
Night-time DHW circulation monitor-
ing switched off
0E:2
Never adjust
0E:0
No heat statement
0F:1
Flow rate adjustable from 0.1 to
to
25.5 l/min.