Function description
EA1 extension
(cont.)
Coding address "1E" in group 1 "General":
"1E:0"
temperature demand adjustable in the
range from 0 to 100 °C
1 V
10 °C set value change
10 V
100 °C set value change
"1E:1"
temperature demand adjustable in the
range from 30 to 120 °C
1 V
30 °C set value change
10 V
120 °C set value change
Output
aBJ
Connection of a central fault message facility.
External H5 extension
For the following connections:
External burner blocking
External safety equipment
Flue gas damper
X12
41
41
150
41
Fig. 39
Vitotronic
A
External extension H5
B
Burner
C
66
Observe coding address "36" in group 1 "General".
!
Please note
Live contacts lead to short circuits or phase fail-
ure.
The external connections must be potential-
free.
Plug
must remain plugged in, even if no connec-
aBÖ
tion is made.