Fault display
(cont.)
Displayed fault
System characteristics
code
94
No solar DHW heating
98
Control mode
99
Control mode
9A
No solar DHW heating
9b
Control mode
9C
No solar DHW heating
9E
Control mode
9F
Control mode
b0
Control mode
b1
Control mode
b5
Control mode
b7
Boiler is regulated by the
temperature controller.
Cause
Short circuit, cylinder tem-
perature sensor,
connection of temperature
sensor
at the solar
%
control module or sensor
at S2 of the Vitosolic.
Lead break, temperature
sensor
/
,
connection at the solar
control module, type SM1.
Lead break, temperature
sensor
,
connection at the solar
control module, type SM1.
Lead break, collector tem-
perature sensor,
connection of temperature
sensor
at the solar
&
control module, type SM1
or sensor at S1 of the
Vitosolic.
Lead break, temperature
sensor,
connection at S3 of the
Vitosolic.
Lead break, cylinder tem-
perature sensor,
connection of temperature
sensor
at the solar
%
control module, type SM1
or sensor at S2 of the
Vitosolic.
No flow rate or flow rate
too low in the solar circuit,
or temperature limiter has
responded.
Fault, solar control mod-
ule, type SM1 or Vitosolic.
Displayed if a fault occurs
at these devices that has
no fault code in the
Vitotronic.
Short circuit, flue gas tem-
perature sensor
Communication error, pro-
gramming unit
Internal fault
Coding card fault
Troubleshooting
Measures
Check sensor at the solar control
unit (see separate installation and
service instructions).
Check temperature sensor
separate installation and service
instructions).
Check temperature sensor
separate installation and service
instructions).
Check sensor at the solar control
unit (see separate installation and
service instructions).
Check sensor at the solar control
unit (see separate installation and
service instructions).
Check sensor at the solar control
unit (see separate installation and
service instructions).
Check solar circuit pump and solar
circuit (see separate installation
and service instructions).
Acknowledge fault message.
Check solar control unit (see sepa-
rate installation and service in-
structions).
Check flue gas temperature sensor
(see page 51).
Check connections and replace
programming unit if required.
Check PCB is plugged in correctly
(see parts list)
Plug in or replace the boiler coding
card (see page 10).