Viessmann Vitotronic 100 Installation And Service Instructions Manual page 30

Electronic boiler control unit
Table of Contents

Advertisement

Coding levels
Calling up coding levels
Which codes are shown depends on the heating sys-
tem configuration.
The codes are divided into groups:
1: "General"
2: "Boiler"
3: "DHW"
4: "Solar"
5: "Heating circuit 1"
6: "All codes std device"
In this group, all codes of the coding levels are lis-
ted in ascending order (except the codes in the
"Solar" group).
7: "Standard setting"
Coding level 1
1. Press OK and
simultaneously for approx. 4 s.
flashes on the display.
2. Use
to select
and confirm with OK.
1
I flashes on the display for the coding addresses in
group 1.
3. Use / to select the group for the required coding
address.
Confirm with OK.
4. Use / to select the coding address.
5. Use / to set the value according to the following
tables. Confirm with OK.
Resetting codes to their delivered condition
Use
to select 7 in the relevant coding level. Confirm
with OK.
When
flashes, confirm with OK.
Note
This also resets codes in the other coding level.
30
6. Exiting coding level 1: Press
or
Automatically after 30 min
Coding level 2
1. Press OK and
simultaneously for approx. 4 s.
flashes on the display.
2. Press OK and
simultaneously for approx. 4 s.
3. Use
to select
. Confirm with OK.
2
I flashes on the display for the coding addresses in
group 1.
4. Use / to select the group for the required coding
address.
Confirm with OK.
5. Use / to select the coding address.
6. Use / to set the value according to the following
tables. Confirm with OK.
7. Exiting coding level 2: Press
or
Automatically after 30 min
.
.